<br /> <br /> <br /> <br /> <br /> <br /> manner to first minimize throttling losses then, for fans with system power of <br /> greater than 1 hp, fan speed shall be adjusted to meet design flow conditions. <br /> Exception: Fan with fan motors of 1 hp or less. <br /> 2. Hydronic systems balancing: Individual hydronic heating and cooling coils shall <br /> be equipped with means for balancing and pressure test connections. Hydronic <br /> systems shall be proportionately balanced in a manner to first minimize throttling <br /> losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to <br /> meet design flow conditions. Each hydronic system shall have either the ability to <br /> measure pressure across the pump, or test ports at each side of each pump. <br /> Exception: Pumps with pump motors of 5 hp or less." <br /> <br /> (14) Amending Section 505.7 Section 505.7 is amended to read: <br /> <br /> "505.7 Electrical energy consumption. (Mandatory). In buildings having individual <br /> dwelling or subtenant units, provisions shall be made to determine the electrical energy <br /> consumed by each tenant by separately metering individual dwelling and subtenant units. <br /> Tenants shall have ready physical access to meters. Meters shall display kWh <br /> consumption and be calibrated in accordance with ANSI C12.1-2008." <br /> <br /> <br /> (15) Amending Chapter 6 Chapter 6, Referenced Standards, is amended by adding the <br /> following specifications to the ANSI and ASTM categories, to read: <br /> <br /> "ANSI <br /> Standard Referenced <br /> reference in code <br /> number Title section number <br /> <br /> C12.1-2008 Electric Meters Code for Electricity Metering .........................505.7 <br /> <br /> ASTM <br /> Standard Referenced <br /> reference in code <br /> number Title section number <br /> <br /> E 408-2008 Standard Test Methods for Total Normal Emittance of <br /> Surfaces Using Inspection Meter Techniques ..................402.1.1.1 #5, <br /> 402.1.1.1 #6, <br /> 402.1.1.1 #8.1.1 <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> 8 <br />