2. Ground Fault Protection: <br /> a. Approved ground fault circuit protection shall be provided for all <br /> feeder and branch circuits below or extending into inundation <br /> level. <br /> 3. Wiring Method and Material: <br /> a. Distribution Equipment. Equipment such as transformers, fuses, <br /> panelboards, switchboards, disconnects, circuit breakers, <br /> controllers and other devices used for control, disconnecting <br /> means, ground fault protection, or overcurrent protection shall be <br /> located above the inundation level, unless made of water -tight <br /> construction. <br /> 4. The director of public works shall have the authority to consider <br /> exceptions to the provisions of the requirements of this section and may <br /> grant variance from the provisions thereof, if local topographic <br /> conditions clearly indicate that the possibility of flooding is not present. <br /> 5. Contractor will provide a certified bench mark on jobsite for flood zone <br /> elevation reference point. <br /> 6. Residential and nonresidential electrical only permit application <br /> requirements: Electrical design drawings stamped and signed by an <br /> electrical engineer registered in the State of Hawai`i. Plans shall <br /> include a site or plot plan showing the certified flood zone elevation <br /> mark. <br /> [Section 9 -25. • .. • • , • • _ .. • , • , • . • • • • .. • • , <br /> . Reserved. <br /> SECTION 14. Chapter 9, article 5, division 1, section 9 -26 of the Hawai`i County Code <br /> 1983 (2005 Edition, as amended) is amended to read as follows: <br /> "Section 9 -26. Permit required; exceptions. <br /> No person shall perform any electrical work or cause or permit the same to be done, <br /> unless a permit therefor has been obtained from the administrative authority with the <br /> following exceptions: <br /> (1) Electric work and installations to which the provisions of this chapter are <br /> expressly declared to be not applicable. <br /> 15 <br />