Laserfiche WebLink
OTHER REQUIREMENTS <br />5.5 Street Lighting <br />A. Street Lighting From an Overhead Electrical Source <br />The customer installs and maintains conductors, conduits, separable connectors, fuse <br />holders, and fuses between the luminaries and the utility's overhead secondary lines or <br />service drop. <br />All parts of street light service drop, street lamps, and their supporting fixtures (including <br />rods, braces and guys) must not be less than 1 foot above, or 2 feet below the level of <br />messenger or conductors supported by messengers. <br />For street lighting systems in new subdivisions and roadway extensions, the customer must <br />submit a set of drawings of his street lighting plans to the utility. <br />Height requirements for pole -mounted street light meter sockets are: 5' minimum, 6' <br />maximum, with preferred mounting height of 5'-6" similar to outdoor meters accessible to <br />pedestrian traffic, as shown in the Metering chapter of this manual. <br />Prima <br />Secondary <br />conductor) <br />Required clear <br />per GO 6 rule E <br />Vertical plane <br />CL <br />Figure 5-11. Street lighting from an overhead electrical source. <br />tical clearance less <br />174" allowed outside <br />2' clear space <br />Centerline of luminaire <br />Z-6" or T -Y nominal <br />Centerline of bracket <br />93 <br />Hawaiian Electric, Inc. • Hawai'i Electric Light, Inc. • Maui Electric, Ltd. <br />