(C) Warning Signs. Entrances to rooms and other guarded <br />Locations that contain exposed live parts shall be marked <br />With conspicuous warning signs forbidding unqualified persons <br />To enter. <br />110.33 Entrance to Enclosures and Access to Working Space. <br />(A) Entrance. At least one entrance to enclosures for electrical installations as described in <br />110.31 not Less than 610 mm (24 in.) wide and 2.0 m (61/2 feet) high shall be provided to <br />give access to the working space about electrical equipment. <br />Art 110.27 Guarding of Live Parts Except as elsewhere required or permitted by this Code, <br />live parts of electrical equipment operating at 50 volts or more shall be guarded against <br />accidental contact by approved enclosures or by any of the following means: <br />(C) Warning Signs. Entrances to rooms and other guarded locations that contain exposed <br />live parts shall be marked with conspicuous warning signs forbidding unqualified persons <br />to enter <br />225.16 Attachment to Buildings. <br />(A) Point of Attachment. The point of attachment to a <br />Building shall be in accordance with 230.26. <br />210.8 Grounds -Fault Circuit -Interrupter Protection for <br />Personnel. <br />(B) Other Than Dwelling Units. All 125 -volt, single-phase, <br />15- and 20 -ampere receptacles installed in the locations <br />Specified in (1) through (5) shall have ground -fault <br />Circuit -interrupter protection for personnel: <br />(1) Bathrooms <br />(2) Kitchens <br />