Laserfiche WebLink
334.15 Exposed Work. <br />(B) Protection from Physical Damage. Cable shall be <br />Protected from physical damage where necessary by rigid <br />Metal conduit, intermediate metal conduit, electrical metallic <br />Tubing, Schedule 80 PVC conduit, or other approved <br />Means. Where passing through a floor, the cable shall be <br />Enclosed in rigid metal conduit, intermediate metal conduit, <br />Electrical metallic tubing, Schedule 80 PVC conduit, or <br />Other approved means extending at least 150 mm (6 in.) <br />Above the floor. <br />Type NMC cable installed in shallow chases or grooves <br />In masonry, concrete, or adobe, shall be protected in accordance <br />With the requirements in 300.4(E) and covered with <br />Plaster, adobe, or similar finish. <br />334.30 Securing and Supporting. Nonmetallic -sheathed <br />Cable shall be supported and secured by staples, cable ties, <br />Straps, hangers, or similar fittings designed and installed so <br />As not to damage the cable, at intervals not exceeding 1.4 m <br />(41/2 ft.) and within 300 mm (12 in.) of every outlet box, <br />348.30 Securing and Supporting <br />Securing and Supporting. FMC shall be securely <br />Fastened in place and supported in accordance with <br />