Loading...
HomeMy WebLinkAboutCOM 1017.000 1996-1998 t September 21, 1998 981036 Mr. Jiro A. Sumada Deputy Chief Engineer Department of Public Works County of Hawaii 25 Aupuni Street Hilo, Hawaii 96720 Dear Mr. Sumada: Subject: Papaikou Wastewater Treatment Plant Operation and Maintenance Inspection Attached for your use is our annual operation and maintenance inspection report for the subject facility. The facility is given an "ACCEPTABLE" rating. No major deficiencies were noted. Should you have any questions, please call Nahid Qadir of our Wastewater Branch at telephone no. 586-4294. Sincerely, THOMAS E. ARIZUMI, P.E. Chief, Environmental Management Division NQ:erm Attachment c: EPA, Region IX (Attn: Mr. Dan Meer, (w/report) /County Council Public Works Chairperson (w/report) Clean Water Branch (w/report) Conan. Na. ~ ~~1 N'lle No. _ S C ad. Too pW PG._---- . u - OCT 0 2 ~ssa OPERATION AND MAINTENANCE INSPECTION REPORT INTRODUCTION Facility: Papaikou Wastewater Treatment Plant Date(s) of Inspection: July 30, 1998 Inspector(s): N. Qadir (WWB) Facility Representative(s)/Job Title: Lyle Hirota - WWTP Superintendent Ph. 961-8338 Herbert Nakano - WWTP Supervisor (T.A.) Ph. 961-8651 BACKGROUND 1. Current status of deficiencies cited in previous inspection reports: Deficiencies that were noted in the previous inspection are as follows: 1. The annual certification of the crane and hoist at the facility had expired; Certification of the crane and hoist were done on 8/14/97. 2. Three violations of the NPDES effluent pH minimum limit. No violations of the NPDES permit since 2197. 2. NPDES Permit Status: Permit Expiration Date: June 30, 1996 The facility's NPDES permit No. HI 0021113 was administratively extended by the Clean Water Branch on September 23, 1996. 3. Enforcement Action: None. 4. Capacity Analysis: Average flow: 0.087 MGD (For the period 711197 to 6130198) Design Flow: 0.350 MGD; Percent of design capacity: 25% Previous year's comparison: There was a decrease of 0.012 MGD from the previous year's average of 0.099 MGD. 5. Modifications/Additions - Planned/Present Construction Status: None. CURRENT INSPECTION 1. Maintenance: Check either: No. of: Preventive Maintenance: x Current - Backlogged Corrective Maintenance: x Satisfactory - Excessive Major (or all) items requiring repair/replacement: None. 2. Reuse: The facility has a DOH approved effluent irrigation plan: Yes No x Not applicable 3. NPDES or Chapter 62 violations (effluent limitations, spills, etc.): None 4. Visual quality of effluent on date of inspection (inspector's judgment): The effluent was noted to be clear on the date of the inspection. 5. Laboratory Data: The following influent and effluent data were collected for the period July 1997 through June 1998: a. Influent BOD5 and TSS averaged 183 mg/l and 198 mg/1, respectively. b. Effluent BOD5 averaged 2.4 mg/l and effluent TSS averaged 2.5 mg/1. 6. Facility's Present Deficiencies: 1. Excessive rust was noted on the blowers. 2. The effluent flow meter was reportedly calibrated but did not have a calibration tag. O&M Report Form (12/93) 2 SUMMARY 1. General Rating: X ACCEPTABLE CONDITIONAL ACCEPTANCE UNACCEPTABLE Explanation: The facility is being operated and maintained satisfactorily. 2. General Comments/Recommendations: 1. The chlorine contact tank (CCT) had excessive solids at the tank's bottom. Denitrified sludge was also noted floating on the treated effluent in the CCT. The tank should be cleaned out more often to prevent solids carryover in the effluent. O&M Report Form (12/93) 3