HomeMy WebLinkAboutCOM 0156.000 2008-2010LINDA LINGLE
GOVERNOR OF HAWAII
s ..
~'+~~9 ~s ~~a4
eI
t/
!~
L ~
~ ~~
~.. ~..,.r'~
STATE OF HAWAII
DEPARTMENT OF HEALTH
P.O. BO% 3318
HONOLULU, HAWAII 96801
February 5, 2009
CERTIFIED MAIL 7002 3150 0001 6551 1658
RETURN RECEIPT REQUESTED
Mr. Ronald Nickel, Civil Engineer
Rdnald Nickel, P.E., LLC
12-7109 Kalaunu Street
Pahoa, Hawaii 96778
Dear Mr. Nickel:
CHIVOME LEINAALA FUKINO, M.D.
DIRECTOR OF HEALTH
In reply, please refer to:
EMD/WB
W W 295 FINAL DEC CL
O t"~
-Z r~-~°
~ :_
"Ci
~-
.L t~";
Subject: Variance Application No. WW 295 Docket No. 08-VWW-2
Received from Edward & Judith Fukuda r:=.}°
Application for Variance -Primarily Concerning
Large Capacity Cesspools Restaurant /Laundromat
at 74 W Kawailani Street, Hilo, Hawaii TMK: (3) 2-2-041: 069
N
P
O
GLl
T
0
-u
3
fV
~+
ea
o"r'
r .
;~~:
~,,
Please find enclosed the Department of Health's Decision and Order regarding the above
mentioned application for variance request which was GRANTED on Monday February 2, 2009
for five (5) years. We are enclosing for your information the Findings of Fact and Conclusions
of Law.
Please note the variance conditions. If there are any questions relating to the variance, please
contact Mr. Tomas See, Chief of the Wastewater Branch at our direct toll free phone number
974-4000 ext. 64294, fax (808) 586-4300.
Sincerely,
THOMAS E. ARIZUMI, P.E., IEF
Environmental Management Division
Enclosures: Final Decision and Order
Findings of Fact and Conclusions of Law
c: Applicant - Mr. & Mrs. Fukuda
Clean Water Branch
Safe Drinking Water Branch
Wastewater Branch -Hilo Staff Engineer
Department of Water Supply -County of Hawaii
strict Health Office -Hilo
-lawaii County Council
FYI -Environmental Planning Office
Comm: No.
Ref. To: 17.20091
Ref. Dote ~f~~---
STATE OF HAWAII
In the Matter of the Application
Variance Application No. WW 295
for Individual Wastewater System
Owners Edward & Judith Y. Fukuda
Primarily Concerning
Large Capacity Cesspools for
Restaurant /Laundromat at
74 W Kawailani Street, Hilo, Hawaii
TMK (3) 2-2-041: 069
DEPARTMENT OF HEALTH
Docket No. OS-VWW-24
DECISION AND ORDER
Pursuant to Chapter 342D, Hawaii Revised Statutes, and Chapter 62 of Title 11,
Administrative Rules and based upon the application and staff review, the Variance Request from the provisions
of Chapter 11-62, Section 11-62-03 and Section 11-62-31.1(a)(2)(D) is hereby GRANTED for five (5) years with
the following provisions:
1. The existing cesspool apparently receives more than 1000 gallons per day (gpd) of wastewater.
Thus, Underground Injection Control (UIC) regulations are applicable, and a UIC permit will be
required to continue the operation of the injection-well cesspool as a seepage pit. We
recommend that the facility's consultant contact Norris Uehara of the UIC program at
(808) 586-4258 to discuss UIC regulatory requirements.
2. Plans for each IWS shall be submitted to the Wastewater Branch for review and approval before
any construction begins. In addition, the treatment IWS shall be approved in writing before being
placed into service.
3. Each septic tank shall be fitted with an effluent filter(s).
4. Pretreatment of all food waste wastewater and non-domestic type wastewater shall be provided prior
to entering the septic tank system. Pretreatment shall meet the requirements of Chapter 11-62.
5. The project shall connect to the County sewer service system should it become available to the
area.
Please contact the Wastewater Branch's Planning & Design Section at (808) 586-4294 for
technical information regarding treatment individual wastewater systems.
6. There is no automatic renewal. Should applicant wish to renew his variance application,
applicant must submit an Application for Variance for renewal.
DATED: Honolulu, Hawaii, Februarv 2 2009
~>
THOMAS E. ARIZUMI, P.E., CHI
Environmental Management Division
Edward & Judith Fukuda -Variance Application WW 295, Docket No. 08-VWW-24 Decision & Order Page 1
STATE OF HAWAII
DEPARTMENT OF HEALTH
In the Matter of the Application
Variance Application No. WW 295
for Individual Wastewater System
Docket No. 08-VWW-24
Owners Edward & Judith Y. Fukuda
Primarily Concerning
Large Capacity Cesspools for
Restaurant /Laundromat at
74 W Kawailani Street, Hilo, Hawaii
TMK (3) 2-2-041: 069
FINDINGS OF FACT AND CONCLUSIONS OF LAW
An application from Edward & Judith Y. Fukuda Trust, Edward Fukuda of 74 W.
Kawailani Street, Hilo, Hawaii for a five (5) year variance from Hawaii Administrative Rules,
Chapter 62 of Title 11, Section 11-62-03 and Section 11-62-31.1(a)(2)(D) was reviewed by the
Department of Health staff. A public notice of the application was printed in the
December 2, 2008 issue of the Honolulu Star Bulletin and the December 8, 2008 issue of the
Hawaii Tribune Herald publications. Three (3) comments pertaining to the application were
received during the 30 days following the publication of the public notice.
Findings of Fact
The individual authorized to act for the applicant, Mr. Ronald Nickel, Civil Engineer,
Ronald Nickel P.E., LLCof 12-7109 Kalaunu Street, Pahoa, Hawaii has applied for alive-year
variance from the Hawaii Administrative Rules (HAR), Section 11-62-03 Definitions state
"Individual wastewater system means a facility which is designed to receive and dispose of no
more. than 1000 gallons per day of domestic wastewater. Individual wastewater systems may
involve treatment processes and include, but are not limited to, septic tanks and household
aerobic units with disposal system and cesspools. Each individual wastewater system shall be
an independent system and shall have all of its plumbing, treatment (if any), and disposal
components separate from any other wastewater systems." and Section 11-62-31.1(a)(2)(D)
"Developments involving buildings other than dwellings. The total wastewater flow into each
individual wastewater system shall not exceed one thousand gallons per day."
The applicant as stated that the total area of the subject parcel is 12,060 square feet.
The lot has one building, the one building contains a small drive in, a Laundromat, a storage
room and a combinations women's/men's toilet. The estimated wastewater flow is 3000 gpd,
1,600 gpd from the Laundromat and 1,400 gpd from the drive in. The property is located at
74 W. Kawailani Street, Hilo, Hawaii TMK: (3) 2-2-041: 069.
Edward & Judith Fukuda -Variance Application WW 295, Docket No. 08-VWW-24
Findings of Fact and Conclusions of Law Page 1
The applicant has made the following comments.
1. The large capacity septic system proposed to serve the facility would not comply
with HAR Section 11-62-03 because the IWS would receive more than 1,000
gallons per day of wastewater. The estimated flow into the system would be
1,400 gallons per day.
2. The existing large capacity cesspool(s) must be closed and replaced with a new
treatment individual wastewater system by April 5, 2005 to comply with federal
requirements.
3. The current State requirement of a wastewater treatment plant would significantly
add to the construction cost as well as require a much greater outgoing
maintenance cost.
4. The facility has been in operation for 52 years in this location using the existing
cesspool. The installation of a wastewater treatment plant is lieu of a septic
system will not be possible due to space restrictions and may force the owner to
abandon the business operation.
5. The applicant believes this variance request is in the public interest because the
LCC will be upgraded to an IWS (septic system). The IWS plans will be
designed by an engineer and will be submitted to DOH for review and approval.
The new IWS will provide a better wastewater treatment system compared to the
existing LCC. Therefore, impact to the environment will be minimized.
6. Prevent loss of jobs. The LCC serving my facility has been in operation for 52
years. The current State requirements of a wastewater treatment plant would
significantly add to the construction cost, as well as require a much greater
ongoing maintenance cost. I (owner) may be forced to close my existing
business and lay off my employees.
7. The existing LCC will be upgraded to an IWS (septic system). The IWS will
provide a better treatment system prior to effluent disposal. The IWS will be
designed and constructed to meet the Department of Health standards. The
impact to the environment will be minimized compared to the current wastewater
disposal.
8. The proposed treatment individual wastewater systems wilt provide greater
protection than the large capacity cesspools. The proposed IWS is an
improvement to the existing cesspool in terms of wastewater treatment. The
septic tank will provide pretreatment and sludge removal prior to effluent
disposal.
9. The owner of the facility simply cannot afford to build and operate wastewater
systems meeting all the requirements of HAR Chapter 11-62 such as small
aerobic wastewater treatment plants.
Edward & Judith Fukuda -Variance Application W W 295, Docket No. OS-VW W-24
Findings of Fact and Conclusions of Law Page 2
10. The variance is requested for the maximum of five (5) years.
11. The following information is from the Information for Variance Evaluation by UIC
Program worksheet, Underground Injection Control (UIC) Program, Safe Drinking
Water Branch:
Facility Address is: 74 W. Kawailani Street Owner: Edward & Judith Y. Fukuda,
Trustee
Island: Hawaii TMK: (3) 2-2-041: 069 Lot Size: 12,060 sq. ft.
Action related to disposal is: reuse cesspool as seepage pit
Existing Cesspool: Elev (g) ft 173, Diameter (d) ft 12, Depth (h) ft 25, Depth to
Standing Water from Surface if present: 18.
Wastewater type: domestic, non-residential, food processing, Laundromat.
Facility's wastewater flow in gallons per day: existing design 3000 gpd. Actual
(measured or metered) Average 3000.
The following agencies submitted the following comments:
The Clean Water Branch submitted the following comment:
Will defer to the Wastewater Branch final decision.
2. The Safe Drinking Water Branch submitted the following comments:
A. Because the proposed improvement is being driven by the Federal ban
on large-capacity cesspools, we have no objection to granting the
variance as proposed; and
B. The existing cesspool apparently receives more than 1000 gallons per
day (gpd) of wastewater. Thus, Underground Injection Control (UIC)
regulations are applicable, and a UIC permit will be required to continue
the operation of the injection-well cesspool as a seepage pit. We
recommend that the facility's consultant contact Norris Uehara of the UIC
program at (808) 586-4258 to discuss UIC regulatory requirements.
The Wastewater Branch states that there is no existing sewer service system
available for connection. We offer the following comments:
A. Plans for each IWS shall be submitted to the Wastewater Branch for
review and approval before any construction begins. In addition, the
treatment IWS shall be approved in writing before being placed into
service.
B. Each septic tank shall befitted with an effluent filter(s).
C. Pretreatment of all food waste wastewater and non-domestic type
wastewater shall be provided prior to entering the septic tank system.
Pretreatment shall meet the requirements of Chapter 11-62.
Edward & Judith Fukuda -Variance Application WW 295, Docket No. OS-VWW-24
Findings of Fact and Conclusions of Law Page 3
D. The project shall connect to the County sewer service system should it
become available to the area.
E. Therefore, upon the agreement of the conditions stated, we recommend
the rantin of this variance application.
Please contact the Planning & Design Section of the Wastewater Branch
at (808) 586-4294 if you have any questions.
Conclusions of Law
Chapter 342D, Hawaii Revised Statutes, Section 342D-7(c), states that no variance shall
be granted by the Department unless the application and supporting information clearly show
that:
The granting of the variance is in the public interest as defined in the Hawaii
Revised Statutes, Section 342D-6(c)(4).
2. The granting of this variance will not substantially endanger human health or
safety.
3. Compliance with the rules, regulations or standards from which the variance is
sought would produce serious hardship without equal or greater benefits to the
public.
Based upon the foregoing findings of fact, it is concluded that the above requirements
have been met.
Comment and Recommendation
Based upon the foregoing findings of fact and conclusions of law, it is my
recommendation that the variance request be GRANTED for five (5) years with the following
conditions:
The existing cesspool apparently receives more than 1000 gallons per day (gpd)
of wastewater. Thus, Underground Injection Control (UIC) regulations are
applicable, and a UIC permit will be required to continue the operation of the
injection-well cesspool as a seepage pit. We recommend that the facility's
consultant contact Norris Uehara of the UIC program at (808) 586-4258 to
discuss UIC regulatory requirements
2. Plans for each IWS shall be submitted to the Wastewater Branch for review and
approval before any construction begins. In addition, the treatment IWS shall be
approved in writing before being placed into service.
3. Each septic tank shall be fitted with an effluent filter(s).
Edward & Judith Fukuda -Variance Application WW 295, Docket No. OS-VWW-24
Findings of Fact and Conclusions of Law Page 4
Pretreatment of all food waste wastewater and non-domestic type wastewater
shall be provided prior to entering the septic tank system. Pretreatment shall
meet the requirements of Chapter 11-62.
5. The project shall connect to the County sewer service system should it become
available to the area.
Please contact the Wastewater Branch's Planning & Design Section at
(808) 586-4294 for technical information regarding treatment individual
wastewater systems.
6. There is no automatic renewal. Should applicant wish to renew his variance
appficatidri, applicant' must submit an Application for Variance for renewal.
DATED: Honolulu, Hawaii, February 2, 2009
/J
~~~~~~~ G~~~ -~
THOM AS~ZUMI, P.E., CHIE
Environmental Management Division
The foregoing findings of fact and conclusions of law are hereby adopted.
Edward & Judith Fukuda -Variance Application VVW 295, Docket No. OS-VWW-24
Findings of Fact and Conclusions of Law Page 5
Transmittal Date:
Wastewater Branch Variance Appli at Docket No. - VWW - APP # WW
Name/Title: w ~ N (
Subject: Final Signed Decision Cover Letter Signed ecision & Order & Findings of Fact & Conclusions
ROUTE TO:
Agent: Q~
Dlrector of Health - Chlyome Lemaala Fukino
Deputy Dlrector for Envlronmental Health Administration -Laurence Lau
Chief, EMD -Thomas E. Arizunti
Attorney General's Office -Deputy Attorney Edward "Ted" Bohlen
Clean Water Branch -Alec Wong
Environmental Planning Office -Kelvin Sunada
Safe Dnnking Water Branch - Stuart Yamada
Sanltatlon Branch - Commercial Properties Only
Wastewater Branch Staff Personnel
[ )Hilo -Jerry Nunogawa (TMKs 1, 2, 3, 4)
[~4.Kona -Dane Hiromasa (TMKs 5, 6, 7, 8, 9)
[ 1 Kauai -Lori Vetter
[ ]Maui -Roland Tejano
vaiw - ~~nnny vng
Water Departments
[ 1 Board of Water Supply -Clifford Lum
l~ County of Hawaii Dept of Water Supply -Milton Pavao
[ 1 County of Maui Dept of Water Supply -Jeffrey Eng
[ 1 Kauai County Department of Water -Edward Tschu p'
[ 1 Maui DHO -Herbert Matsubayashi, District Environmental Health Program Chief
[ ]Kauai DHO - ,District Environmental Health Program Chief
[7'~1-klilo DHO -Aaron Ueno, District Environmental Health Pro ram Chief
City & County of Honolulu, Department~of Plannin & Permitting
[ 1 County of wa Council / [ ]Honolulu City & County Council
Dahu Neighborhood Board #
NO ACTION REQUIRED:
~( Here is the FINAL SIGNED Decision & Order and Findings of Fact & Conclusions of Law.
The attached is for your information to file or discard at your discretion. No action is
required. Thank you for your assistance in the variance application ororaca
From: Department of Health -Wastewater Branch
919 Ala Moana Blvd. Room 309
Honolulu, Hawaii 96814-4920
phone (808) 586-4294 fax (808) 586-4300
Law