HomeMy WebLinkAboutCOM 0128.076 2010-2012Software Tool for
Hawaii State Energy Conservation Code
Area - Weighted Average Solar Heat Gain Coefficient
Template Instructions
July 2011
Purpose of the Template
The template provides a method to calculate the area - weighted average SHGC as allowed
by Sections 402.3.2 and 502.3.3 of IECC 2009, as amended.
Intent of the Template
The template approach recognizes the benefit of architectural shading and window
screens in reducing solar heat gain through windows in Hawaii.
Genesis of the template approach
During the State Building Code Council meeting a written request to exempt jalousie
windows from SHGC requirements was submitted. The subsequent discussion brought to
light the SHGC exemptions being implemented in the Hawaiianized IECC that, when
used with the area - weighted average SHGC approach of Section 402.3.2, would allow
jalousie windows. A comment was made that it was not clear how to calculate the area -
weighted average SHGC. Based on this discussion, the Chairman of the State Building
Code Council requested that Howard Wiig of DBEBT develop a template to calculate the
area - weighted average SHGC. Paul Norton of the National Renewable Energy
Laboratory agreed to assist DBEDT with the template with the assistance of industry
participants.
Exemptions and allowances included in the area - weighted average SHGC template
North - facing windows are assigned a SHGC of 0.00.
Opaque louvered openings are assigned a SHGC of 0.00
Windows with a projection factor greater than or equal to 1.0 are assigned a
SHGC of 0.00.
Windows with projection factors between 0.25 and 1.0 are credited through
reduced SHGC weighting
Exterior screens are credited at their full SHGC
Interior screens are given 1/3 the credit of their full SHGC
The 15 sf exemption given in Sections 402.3.3 and 502.3.3 is included
Template Input Instructions
The template is designed to calculate the area- weighted average SHGC for a specific
existing home or new home design. To provide credit for orientation, window shading
and window screens, information on the area, SHGC, orientation, overhang, and screen
of each window must be entered into the template. The template then calculates the area -
weighted- average SHGC.
Comm. No. /24 . 7‘
Ref. ToNaariii
Ref. Date fltyT
If a specific window package design does not meet the required SHGC, the template can
be used to explore the effects of design changes on the weighted - average SHGC.
Information for each window in the home must be entered into one row in the template.
This approach allows for a diversity of window types, overhangs, and screen
configurations. The number of rows in a completed template should equal the number of
windows in the home. The template is color coded as follows:
- Enter window information in these cells. This is mandatory information.
- Enter window information in these cells. This is optional information.
Yellow cells
White cells
— These cells are calculated and locked. Do not enter information.
Required Window Information
You will need to know the following information on each window to complete the
template:
Mandatory information on each window:
- Orientation
Height
Width
Glazing material
SHGC
Optional information on each window:
- Overhang horizontal distance (if overhang is present)
Overhang vertical distance (if overhang is present)
Screen SHGC (if screen is present)
Location of screen — interior or exterior (if screen is present)
Percent of window covered by screen (if screen is present)
Step -by -Step input Instructions for Entering One Window
Column B: Orientation of Window
Click on a cell in column B and an arrow for a pull -down menu will appear. Choose the
correct orientation for the window.
North- facing windows are exempt from the SHGC requirements. The north - facing
window areas receive a weighting factor of 0.00 in the area - weighting average SHGC
calculation. All other orientations receive a weighting factor of 1.00.
A north - facing window is defined as any window that faces within 22.5 degrees of true
north. You can determine if a window qualifies as north - facing by using a compass. In
Hawaii true north is 10 degree east of magnetic north (this is called the magnetic
declination.) Therefore any window facing between 347.5 and 32.5 on the compass is
north facing. Stand with your back to the window and point directly away from the
window. If the compass needle is between 347.5 ° and 32.5 ° as shown in the diagram
below, then the window is considered to be north- facing.
True
North
Columns D and E: Height and Width
Enter the height and width of the window in inches in columns D and E.
You may round to the nearest inch. The height and width should include framed window
area (not just the glass), because the framed area is included in the National Fenestration
Rating Council (NFRC). SHGC rating of the window.
Column 1: Glazing Material
Click on a cell in column I and an arrow for a pull -down menu will appear. Choose glass
or opaque material for the window.
Because opaque louvered openings are considered windows, this column is used to
determine if the window is glass or opaque material.
Column J: SHGC
Enter the rated NFRC SHGC rating of the window.
This information is contained on the NFRC sticker on new windows and is listed in
window specifications from manufacturers for design purposes. For windows not tested
by the NFRC, the default values listed Table 303.1.3(3) in the IECC 2009 shall be used.
Columns L and M: Shading Horizontal and Vertical Distances
If the window has an overhang, enter the horizontal distance A in column L and the
vertical distance B in column M. If there is no overhand, leave these cells empty.
The horizontal distance A is defined as the "Distance measured horizontally from the
furthest continuous extremity of any overhang, eave, or permanently attached shading
device to the vertical surface of the glazing. Measured in inches."
The vertical distance B is defined as the "Distance measured vertically from the bottom
of the glazing to the underside of the overhang, eave, or permanently attached shading
device. Measured in inches."
Measure directly to the glass (not the window frame) for these distances.
Some examples of A and B distance measurements for different overhang types are given
below:
Simple Overhang
Wall
Overhang
Window
Glazing
A= 36 " --I
B =36"
Sloped Overhang
Wall
Window
Glazing
Offset Overhang
Wall
Window
Glazing
Overhang
B =36"
A =36"
B =56"
Column P: Actual SHGC of Screen
If there is a screen on all or part of the window, enter the SHGC of the screen.
The SHGC of the screen should be available from the manufacturer. If the screen has not
been rated, use a default value of 0.70.
Column Q: Interior /Exterior Screen
Click on a cell in column Q and an arrow for a pull -down menu will appear
If there is a screen on all or part of the window, choose whether the screen is exterior
(outside the glass) or interior (inside the glass).
Column R: % of Window Covered by Screen
If there is a screen on all or part of the window, enter the percent of the window that is
covered by the screen.
For example, if there is screen over half of the window glass, then enter 50 %. If the
screen covers the whole window, enter 100 %. If there is no screen on the window, leave
the default of 0% in this cell.
Column G: Exemptions Applied
Once the entries above have been entered for all windows, enter a total of 2160 in2
(15 ft2) in column G.
IECC 2009 section 402.3.3 states that "up to 15 square feet of glazed fenestration per
dwelling unit shall be permitted to be exempt from .... SHGC requirements... " Column
G allows the template user to designate which window in the home will be used for the
15 ft2 (2160 in2) exemption. Exempting the window(s) with the highest SHGC and least
shading will minimize the weighted- average SHGC for the home.
The 2160 in2 can be broken up and entered in different rows, as long as the area in any
given row does not exceed the area of the window in that row and the sum of all areas
entered in column G is equal to or less than 2160 in2.
Explanation of Key Calculations
Column O. SHGC PF Multiplier
This column assigns a SHGC multiplier according to the projection factor of the window
opening. The multiplier is assigned according to the table below. These multipliers are
equivalent to the SHGC requirements for commercial buildings in IECC 2009 Table
502.3 with the exception that a PF equal or greater than one is assigned a SHGC
multiplier of 0.00.
Projection Factor
SHGC multiplier I
0.00 .
Equal or greater than 1.0
Equal or greater than 0.50 and less than 1.0
0.625
Equal or greater than 0.25 and less than 0.50
0.75
Less than 0.25
1.00
Column S: Effective SHGC of Screen
The SHGC of screens on the exterior of the windows are given full credit. However,
some research indicates that screens on the interior of the windows is about 1/3 as
effective as exterior screens'. For exterior screens, the effective SHGC is calculated as:
Effective SHGC for interior screens = 1— (1- SHGC) /3
Column T: Screen Multiplier
This column calculates the screen SHGC multiplier based on the effective SHGC of the
screen and the percentage of the window covered by the screen.
Screen multiplier = (term for area covered by screen) + (term for uncovered area)
= (Effective SHGC of screen x % covered) + (1 - % covered)
Column U: Total Effective SHGC
The total effective SHGC is the actual window SHGC with all the multipliers applied:
Total Effective SHGC = Window SHGC x Orientation multiplier Material multiplier x PF multiplier
Screen multiplier
Column V: Weighting
The weighting for each window =
Window area after exemptions x Total Effective SHGC
Weighted - Average SHGC
The Weighted - Average SHGC = The sum of all weightings /total window area
` Brugger, A. et.al., Measurement of the Solar Heat Gain Coefficient and U Value of Windows with Insect
Screens, ASHRAE SE- 99- 15 -04, 1999.
vi.uioa, coc''—R.c'c'Cs, o!ZG:1Aoccui<r.,rs /Amu ,_Fo,c._F/../Eg<
'O1
ORDINANCE NO. 890
BILL NO. 2332, Draft 2
A BILL FOR AN ORDINANCE AMENDING CHAPTER 12, ARTICLE 6, OF THE
KAUAI COUNTY CODE -1987 RELATING TO THE ENERGY CODE
BE IT ORDAINED BY THE COUNCIL OF THE COUNTY OF KAUAI, STATE
OF HAWAII:
SECTION 1. Chapter 12, Article 6 of the Kauai County Code - 19857, as
amended, is hereby amended to read as follows and all other and prior ordinances or
parts of ordinances in conflict herewith are hereby repealed.
ARTICLE 6. ENERGY CODE
Section 12 -6.1 Purpose.
This ordinance is for the purpose of adoption and incorporation by
reference the 2009 Edition of the International Energy Conservation Code as
the Energy Code; providing amendments thereto, regulating the construction,
alteration or equipment of buildings or structures in the County of Kauai. This
code will recognize the need for a modern, up -to -date energy conservation code
that addresses the design of energy - efficient building envelopes and installation
of energy efficient mechanical, lighting and power system through requirement
emphasizing performance.
Section 12-6.2 Title.
This Article shall be known as the Energy Code of the County of Kauai,
and may be cited as the "Energy Code."
Section 12 -6.3 Adoption of the International Energy Conservation
Code.
The International Energy Conservation Code (IECC), 2009 Edition as
copyrighted and published in 2009 by the International Code Council,
Incorporated, 4051 West Flossmoor Road, County Club Hills, Illinois, 60478-
5795, is by reference incorporated herein and made a part hereof as the Energy
Code, subject to the following amendments.
Section 12 -6.4 Local Amendments to the IECC.
(1) Amending Section 101.1. Section 101.1 is amended to read as follows:
101.1 Title. This code shall be known as the Energy
Conservation Code of the County of Kauai. and shall be cited as such.
It is referred to herein as "this code."
(2) Amending Section 101.2. Section 101.2 is amended to read as follows: