December 11,2015 R
The Honorable Dru Kanuha, Council Chairperson and
Members of the Hawai`i County Council
Hawai`i County Council
25 Aupuni Street
v1
Hilo, Hawai`i 96720 v �'
Dear Chair Kanuha and Council Members,
In accordance with Hawaii County Charter Section 3-18(d)(2), attached is the Office of the Legislative Auditor's
report of our audit of Variable Frequency Drives(VFDs)at County of Hawai`i's Department of Parks and
Recreation swimming pools. The purpose of the audit was to evaluate the cost effectiveness of installing these
VFDs at swimming pools countywide.
In 2006,the Department of Parks& Recreation(P&R)began taking proactive cost savings measures by installing
VFDs at three of its swimming. However, P&R has not had program objectives for reducing costs since Fiscal
Year 2012-2013 and has not installed VFDs at any of the remaining pools. By installing VFDs,we estimate the
County could annually save approximately$122,578 in electricity costs.Furthermore,the County should recoup
installation costs within the first three years. After this point, all electrical cost savings are in favor of the County.
If you need any further information,please let me know. We would like to thank the Department of Parks and
Recreation staff for their assistance and cooperation during this audit. We greatly appreciate all of their valuable
time and efforts spent on providing us information.
Respectfully,
C-
Bonnie S.Nims, CGAP
Legislative Auditor
cc: William P. Kenoi, Mayor
Stewart Maeda,County Clerk
Clayton S. Honma, Director, Department of Parks and Recreation
Deanna Sako,Director,Department of Finance
Walter Lau, Managing Director Comm. No. 6 0 C 3
Ref. To:
Ref. Dote DEC 1 8 2015
Hawai`i County is an Equal Opportunity Provider and Employer
Performance Audit Report
Variable Frequency Drives (VFDs)
at
County of Hawai ' i 's
Department of Parks & Recreation
Swimming Pools
Report No. 2015-03
,r ,, ,,1' '''.'f'',! ::C;r''' 4'4‘.,'''...' ''''.'''''. #'42'..' .' r*,-,f,_-:,,,4-
-.0-.,....;44;7171.., :-7.4,-,-*--'-',7'Hi:-".: ..:.'rt.;.:.'?*:',k:f'15:.--:";:' ,.&,'`--:,.,,,..4.0„.'; ',4 4,''
-;4., t'-'4,14-°410..--„,:, ,,,,,!'*, . - .' 7:-'.- ,' rt„,-„.„1„-. i:.:$
„_,. ..,,,,:i.40/1„‘. 1. _ , , .
„4,„_.„,..„ ..,,,„_, ,.. „,,,m,,,,,. , .. ,,,
,,„?, ,---- -..„,..„..„,.:,44,,.„*„xf 1,:-.,„, -._ r ---'''.-WP t*
ipzi,IVI%..:. .--.1 '1,''':.''‘‘. '''-'''''''' ---,,,w, ... '
December 11 , 2015
..--;01‘.1.°.t
O,NTY OF Nq�91,
` Office of the Legislative Auditor
County of Hawaii
This page intentionally left blank.
Dru Mamo Kanuha ..... Bonnie S.Nims,CGAP
Chair&Presiding Officer /..).151.c:T~".rq� Legislative Auditor
Council District 7 47,-
Business Address
` '>'^• ".°• *= 1266 Kamehameha Avenue
,r8 OF MPS "
Suite A-8
Hilo,Hawai`i 96720
(County of linfintri
OFFICE OF THE LEGISLATIVE AUDITOR
25 Aupuni Street Hilo, Hawai`i 96720 * (808)961-8386 * Fax(808)961-8905
website:htty:-:'Hawai"icounti y.gov e-mail:puhl iclao(ic,co.Hawai I hi.us
December 11, 2015
The Honorable Dru Kanuha, Council Chairperson and
Members of the Hawai`i County Council
Hawai`i County Council
25 Aupuni Street
Hilo, Hawai`i 96720
Dear Chair Kanuha and Council Members,
In accordance with Hawai`i County Charter Section 3-18(d)(2), attached is the Office of the Legislative Auditor's
report of our audit of Variable Frequency Drives(VFDs)at County of Hawai`i's Department of Parks and
Recreation swimming pools. The purpose of the audit was to evaluate the cost effectiveness of installing these
VFDs at swimming pools countywide.
In 2006,the Department of Parks&Recreation(P&R)began taking proactive cost savings measures by installing
VFDs at three of its swimming. However, P&R has not had program objectives for reducing costs since Fiscal
Year 2012-2013 and has not installed VFDs at any of the remaining pools. By installing VFDs,we estimate the
County could annually save approximately $122,578 in electricity costs. Furthermore,the County should recoup
installation costs within the first three years. After this point, all electrical cost savings are in favor of the County.
If you need any further information,please let me know. We would like to thank the Department of Parks and
Recreation staff for their assistance and cooperation during this audit. We greatly appreciate all of their valuable
time and efforts spent on providing us information.
Respectfully,
Bonnie S.Nims, CGAP
Legislative Auditor
cc: William P. Kenoi, Mayor
Stewart Maeda, County Clerk
Clayton S. Honma, Director, Department of Parks and Recreation
Deanna Sako, Director, Department of Finance
Walter Lau, Managing Director
Hawai`i County is an Equal Opportunity Provider and Employer
This page intentionally left blank.
In Brief
Background What we found
A Variable Frequency Drive (VFD) is an In 2006, the Department of Parks & Recreation (P&R)
electrical device designed to monitor and protect began taking proactive measures by installing Variable
a swimming pool/spa filtration or water feature Frequency Drives (VFDs) at three of its swimming pools
pump by varying the frequency or speed of the including Charles "Sparky" Kawamoto Swim Stadium,
motor in order to provide a specific flow rate. Pahoa Community Aquatic Center (PCAC), and
Research has shown that VFDs reduce costs Laupahoehoe Swimming Pool (no longer in use). P&R
and usage of electricity and energy, potentially has not had program objectives for reducing costs since
recouping the cost of purchasing and installing a Fiscal Year 2012-2013 and has not installed VFDs at
VFD in less than a year. any of the seven remaining pools.
The Department of Parks & Recreation (P&R), Historic average monthly electrical savings of installing
Aquatics Division is responsible for programs these VFDs ranged from 23 percent (PCAC) to 63
and operation of nine public swimming pools. percent (Kawamoto). By installing VFDs countywide,
They also develop and implement a we estimate an annual cost savings of approximately
comprehensive water safety program by $122,578. Furthermore, the County should recoup
providing lifeguard services at County swimming installation costs within the first three years. After this
pools. point, all electrical cost savings are in favor of the
County.
Why we did this audit Management generally agreed with the comments and
While performing a risk assessment at P&R, we recommendations in this report. Their complete
response to this audit can be found on pages 13:
found that installing VFDs at County swimming Management's Comments.
pools could reduce operating costs.
The objective of the audit was to evaluate theme What we recommended
cost effectiveness of installing Variable The recommendations identify actions for management
Frequency Drives (VFDs) at swimming pools to increase cost-effective measures at County-owned
countywide. pools by:
• Reinstating P&R's previous program measures
related to reduction of utility costs at all facilities
by implementing green technologies and
f
proactive practices, or at a minimum, develop a
new program measure that addresses reduction
, . 5. . of cost and/or energy savings.
• Developing and implementing a written plan for
installing VFDs at all County operated swimming
pools. Then incorporate the plan into future
fiscal years' budget that will reflect the
Kona Community Aquatics Center, Kailua-Kona, HI
Photo courtesy of the Department of Parks&Recreation installation of VFDs and reduction of electricity
expenditures.
Table of Contents
Introduction 1
Background 2
Audit Objectives 4
Audit Scope and Methodology 4
Commendations and Noteworthy Achievements 5
Audit Results 6
The Department of Parks & Recreation has not installed VFDs, which have a
proven history in reducing monthly electricity costs, at seven of its swimming
pools 6
Why have more VFDs not been installed? 8
What is the effect of installing VFDs? 9
What is the installation cost for a VFD? 10
Recommendations 12
Management's Comments 13
Appendix A—Audit Criteria 14
Appendix B—Detailed Pool Electricity Costs 19
Introduction
The Office of the Legislative Auditor conducted this performance audit of Variable Frequency
Drives (VFDs) at County of Hawai`i's Department of Parks & Recreation' (P&R) Aquatics
Division pursuant to Section 3-18 of the Hawaii County Charter, which outlines the Office of the
Legislative Auditor's primary duties.
Performance audits typically examine the effectiveness, economy, or efficiency of a government
program. They can include analyzing the services of an entire department or activity, identifying
possible cost savings, identifying the outcomes achieved by a program, or comparing actual
department practices against the practices called for in law or policy.
Our objective in performance auditing is to improve public services provided by county
government. We do this by recommending specific actions that will address the issues we raise
and by providing valuable information to the public, the administration, program leadership, the
Hawaii County Council, and the Mayor.
A performance audit of the VFDs at P&R was included in the Fiscal Year 2014-2015 annual
audit plan based on the results of our countywide risk assessment.
Variable Frequency Drives at County Pools: Introduction l 1
Background
What is a Variable Frequency Drive (VFD)?
A Variable Frequency Drive (VFD) is an electrical device, normally wall-mounted, designed to
monitor and protect a swimming pool/spa filtration or water feature pump. They also vary the
frequency or speed of the motor in order to provide a specific
flow rate and are installed on the electrical line between the
electrical breaker panel, and the pool pump.
k
S ;
f
How does a VFD work?
VFDs vary the speed of a pool pump to match the pressure k
or flow requirements and achieve energy savings. Since pool
pump systems run continuously and are typically oversized,
energy consumption is high. These systems are oversized to
help ensure proper filtration and chemical treatment as well
as compensate for clogged filters and maximum pool
occupancy. By adding a VFD, the motor speed of the pool
pump can be decreased while running the filtration system's
valves wide open to allow for maximum flow. When VFD Control panel at Kawamoto
regulating flow, putting a VFD on a time clock enhances Swim Stadium, Hilo, HI
efficiency. For example, a pool running around the clock at Photo courtesy of the Department
100 percent can now run at 90 percent during operational of Parks & Recreation
hours and 60 percent during non-operational hours.' This
reduces energy consumption and costs.
As shown in Illustration 1, the VFD works by converting incoming AC power to DC power,
smoothing or conditioning it and delivering modified power to the motor. By varying the
frequency of this power, the motor speed is reduced, thus reducing both the flow rate and the
amount of energy consumed. The addition of a VFD to a pool pumping system can offer
dramatic potential energy savings, while protecting the motor at the same time. This is done
completely automatically and without operator involvement, allowing continuous speed and flow
control. The ability to adjust motor speed enables closer matching of motor output to load and
often results in very large energy savings.
1 VFDs and Pool Pumps(EMA Drives and Automation) http://www.emainc.net/newsletter/vfd-s-and-pool-
pumps/
Variable Frequency Drives at County Pools: Background 12
Sine Wave Variable Mechanical
Power Frequency Power
I\/- Power AC Motor
Variable
Frequency
Controller Juiium
y 1 540
o / ' Power Conversion Power Conversion
► ►
Operator
Interface
Source: en.wikipedia.org
Illustration 1
How do VFDs reduce costs?
Research and testimonies have shown that VFDs reduce costs and usage of electricity and energy.
Some examples of electrical savings include:
• Instead of turning off the pump, pumps can be turned down with a VFD.
• VFDs are a tremendous source of energy savings while not sacrificing pump longevity or
performance.
• Major savings are expected in most applications as pool pumps are generally oversized by
design, and must be trimmed back with proportioning valves.
• VFDs protect against surges, brownouts and other on-site power issues.
• VFDs work by varying the "speed" of the motor to provide the desired water flow rate.
• VFDs also reduce the power company"Demand Charges" (the surcharge paid by larger
power customers), so an entity will pay less for the electricity property-wide, which this
savings is applied to the entire electric bill, not just the swimming pool or spa portion.
• During normal operations, pumps used for circulating, filtering, and heating can be operated
at 80 percent of peak capacity due to more efficient piping runs, and/or oversized pumps
(51.2 percent of normal power).
• During off-peak operations, some pumps could be operated at 50 percent of peak capacity
while still circulating, filtering, and heating (12.5 percent of normal power).2
2 Alvaro Mendoza,Aquatic Facility Design&Optimization, Pitfalls and Opportunities(United States Swim School
Association,2013)http://www.usswimschools.org/
Variable Frequency Drives at County Pools: Background 13
Audit Objectives
While performing a risk assessment of the Department of Park and Recreation (P&R), we found
that installing Variable Frequency Drives (VFDs) at County swimming pools could reduce
operating costs. The objective of the audit was to evaluate the cost effectiveness of installing
VFDs at swimming pools countywide.
Audit Scope and Methodology
To accomplish our objective, we:
• Developed an understanding of VFD operations and its process;
• Corroborated information through interviews with appropriate personnel, reviewed
documentation, and performed site visits of actual pool operations;
• Analyzed expenditures related to swimming pool activities;
• Determined cost savings of expenditures, if any, related to pools after VFD installation;
and
• Determined best practices of installed VFD in related swimming pools.
This performance audit focused on swimming pool expenditures related to the installation of
VFDs to pumps and motors currently at three County Swimming Pools:
• Charles "Sparky" Kawamoto Swim Stadium (Kawamoto). The VFD was installed
during the months of June 2006 through September 2007; we therefore reviewed
monthly electricity costs before and after the installation of the VFD for both Fiscal Year
2006-2007 and Fiscal Year 2007-2008.
• Laupahoehoe Swimming Pool. The VFD was installed during the months from
September 2008 through May 2009; we therefore reviewed monthly electricity costs
before and after the installation of the VFD for Fiscal Year 2007-2008 and Fiscal Year
2008-2009.
• Pahoa Community Aquatic Center(PCAC). The VFD was installed during the months
from May 2013 through September 2013; we therefore reviewed monthly electricity costs
before and after the installation of the VFD both Fiscal Year 2012-2013 and Fiscal Year
2013-2014.
We conducted this performance audit in accordance with generally accepted government
auditing standards. Those standards require that we plan and perform the audit to obtain
sufficient, appropriate evidence to provide a reasonable basis for our findings and conclusions
based on our audit objectives. We believe the evidence obtained provides a reasonable basis
for our findings and conclusions based on our audit objectives. Our conclusions on the
effectiveness of these controls are detailed within this report.
Variable Frequency Drives at County Pools: Objectives,Scope, &Methodology 14
We thank the Department of Parks and Recreation's staff for their assistance and cooperation
during this audit. Management generally agreed with the comments and recommendations in
this report. Their complete response to this audit can be found on pages 13: Management's
Comments.
Commendations & Noteworthy Achievements
The Department of Parks and Recreation took the initiative of installing VFDs in three of its nine
swimming pools and has already proven to reduce electricity cost after installation.
These three pools include:
• Charles "Sparky" Kawamoto Swim Stadium;
• Laupahoehoe Swimming Pool (no longer in use); and
• Pahoa Community Aquatic Center.
We have described details of the realized cost savings in the Audit Results section on page 6.
Variable Frequency Drives at County Pools: Commendations& Noteworthy Achievements 15
Audit Results
The Department of Parks & Recreation has not installed VFDs,
which have a proven history in reducing monthly electricity costs,
at seven of its swimming pools.
In 2006, the Department of Parks & Recreation (P&R) began taking proactive measures by
installing VFDs at three of its swimming pools including:
• Charles "Sparky" Kawamoto Swim Stadium (2007);
• Laupahoehoe Swimming Pool (2009); and
• Pahoa Community Aquatic Center (PCAC) (2013)
Subsequently, the VFD at the Laupahoehoe Swimming Pool burned out in December 2011
since it was stored with corrosive pool chemicals. The VFD has not been fixed or replaced and
remains un-working.
During this time, P&R hired a consultant to assess if County-owned swimming pools needed
repairs and maintenance. The consultant issued a report titled "Countywide Swimming Pools
Assessment and Repairs—September 2007" on September 27, 2007. The report identified five
swimming pools (PCAC, NAS, Kohala, Honokaa, and Pahala) that required repairs including the
replacement of existing pumps and VFD installation. The Department of P&R installed a VFD at
the Pahoa Community Aquatics Center (PCAC) in 2013. The other four pools (NAS, Kohala,
Honokaa, and Pahala) have not undergone any repairs, replacements, or installation of VFDs
as of the date of this report.
To determine if installing VFDs in County-owned pools resulted in a reduction in electricity
costs, we reviewed the four months prior and four months after VFD installation of all utility cost
data (electricity, water, gas, etc.) for the three swimming pools with VFDs. We then compared
the data as shown in Appendix B on page 19, and found substantial decreases in electricity
costs ranging from 23 percent to 63 percent after the County installed VFDs as shown in
Illustration 2.
Variable Frequency Drives at County Pools:Audit Results 16
How much has the County saved by installing VFDs?
(Average Monthly Electrical Costs)
Kawamoto Laupahoehoe Pahoa Community
Swim Stadium Swimming Pool Aquatic Center
(installed 2007) (installed 2009) (installed 2013)
42%
63%
llir
ile;
16 $3,279 $3,549 $2,042`' E $9,251 $7,148
Average Average Average Average Average Average
monthly monthly monthly monthly monthly monthly
costs prior costs costs prior costs costs prior costs
to VFD after VFD to VFD after VFD to VFD after VFD
Note:Variable Frequency Drive (VFD) is an electrical device designed to monitor and protect a
swimming pool/spa filtration or water feature pump. They also vary the frequency or speed of the motor
in order to provide a specific flow rate and are installed on the electrical line between the electrical
breaker panel, and the pool pump
Illustration 2
Variable Frequency Drives at County Pools:Audit Results 17
Why have more Currently, P&R neither has formal written plans nor budgets for
VFDs not been installing more VFDs at its swimming pools.
installed?
The Department of P&R does not have a formal written plan for installing
more VFDs at its remaining swimming pools and their intention for
resuming the installation of more VFDs is dependent on the Department's
funding and budget. The Department of P&R indicated they were
planning to replace the Laupahoehoe VFD when funds were available to
retrofit the VFDs in the remaining pools. However, currently no funds
have been budgeted or designated for additional VFD projects.
Best practices for planning and budgeting process indicates the
developing of strategies; developing of capital plan; budgeting for that
plan; monitoring the plan; and measuring and reporting on the results of
the plan is key to successfully obtaining its goals and objectives.
Illustration 3 illustrates this best practice.
Strategies
Performance Capital Plans
Measurement
Monitoring Budgets
and Control
Source: http://www.cipplanner.com/solutions/pages/capitalplanninq.aspx
Illustration 3
Elimination of key Program Objectives of cost reduction
measures
The Department of P&R Aquatics Section has not had program
objectives for reducing costs since Fiscal Year 2012-2013. Each fiscal
year, the County of Hawaii departments develop their departmental
Variable Frequency Drives at County Pools:Audit Results 18
program objectives along with their proposed operating budget. In
reviewing the County of Hawaii's Fiscal Year 2012-2013 proposed
operating budget (dated March 1, 2012), P&R Aquatics Section's
program objectives listed 12 objectives. Number 11 of these objectives
states "Reduce utility costs at all facilities [emphasis added] by
implementing green technologies and proactive practices." Number 12
additionally states, "Reduce chemical costs at all facilities by prudent
work practices, education and new technologies." Subsequent fiscal
years' proposed operating budget eliminated both program objectives. In
recent years, the County of Hawai'i has experienced hard financial and
economic times while departmental budgets remained status quo or were
significantly reduced. Hence, it would have been appropriate for P&R —
Aquatics to retain and implement these two specific cost reduction
program objectives.
What is the effect Installation of VFDs will result in an estimated annual cost
of installing savings of$122,578.
VFDs?
To calculate the amount of potential cost savings to the County by
installing VFD controllers, we determined the actual cost of electricity for
all County pools for Fiscal Year 2013-2014 (see Illustration 4, column
Actual FY2014). Using electricity costs for the four months prior and the
four months after the VFDs were installed, we found that PCAC's
electricity costs were reduced 23 percent. When the VFD was working
properly at Laupahoehoe, electricity costs were reduced by 42 percent.
Using an average of these two pools, the approximate electricity cost
reduction is 33 percent. We then applied this cost reduction to the
remaining pools as illustrated below. By applying the same electricity
cost reduction percentage for one, three, and five years, potential savings
in electrical costs were $122,578, $367,735 and $612,891 respectively
(see Illustration 4). The Pahala pool was not included since the local
school pays the electric bill (this has not changed since the County
assumed operations of the swimming pool). We also did not include
PCAC in our calculation of potential cost savings since a VFD controller
has already installed. In addition, we did not include Kawamoto Swim
Stadium since the pool has a partial roof-like covering while all other
County pools are open and exposed to the elements without any roof
type coverings.
Variable Frequency Drives at County Pools:Audit Results 19
Potential Cost Savings for One, Three, & Five Years
By Installing VFDs
Actual
Pool FY2014* 1 year 3 year 5 year
Honoka'a $31,916
Kohala $39,772
Kona Aquatics Center $186,843
Konawaena $46,557
Laupahoehoe $40,816
NAS $25,545
Total $371,449
Cost reduction rate as
determined by historic cost 33% x 1 x 3 x 5
savings
Potential Savings $122,578 $367,735 $612,891
"Source: Electricity cost data for FY2014 was provided by P&R Aquatics Section.
Illustration 4
What is the The County should recoup installation costs within the first
installation cost three years. After this point, all electrical cost savings are in
fora VFD? favor of the County.
To determine the cost of installing VFDs at pools countywide, we
reviewed several VFD distributers for VFDs and pumps and found costs
ranged from $2,000 for a 3-Phase 5 horsepower pump to approximately
$6,350 for a larger 20 horsepower 3-Phase pump. The comparable 3-
Phase 5 horsepower VFD ranged from $1,346 to approximately $5,764
for a 3-Phase 20 horsepower VFD.
We also examined PCAC's installation costs from 2013. Since PCAC is
an Olympic sized pool, it required the installation of two motors and two
VFDs totaling approximately $60,000. The approximate labor cost was
$25,000. Hence, the total installation cost for an Olympic sized pool was
approximately $85,000. The County has three Olympic size swimming
pools: PCAC, Kawamoto, and Kona Community Aquatic Center. Two of
these three pools have already had VFDs installed (PCAC and
Variable Frequency Drives at County Pools:Audit Results 110
Kawamoto). The remaining six pools are all smaller and the specific cost
of installing VFDs would depend on current condition of equipment
already in use and the size of the pool.
Using the PCAC installation costs, VFD and pump installation at the one
remaining Olympic size swimming pool should cost approximately
$85,000. Since the remaining six smaller pools would theoretically
require only one pump and one VFD, we estimate installation costs at
approximately half, or$42,500. Using these numbers (one pool at
$85,000 and six pools at $42,500), total costs of installing VFDs
countywide would be approximately $340,000. Comparing the
installation costs to the potential energy cost savings, the County could
potentially recoup the costs in three years (the three-year energy cost
savings was determined to be approximately $367,735).
When either replacing a filtration system (VFD, pump, and motor) or
replacing each component separately, obtaining compatible VFDs,
pumps, and motors is critical for system operational efficiency and
achieving an objective for cost reduction of electricity and usage.
Therefore, P&R should assess each pool's circulation system separately
to determine the proper components needed at each pool to maximize
operational efficiency and to recognize electricity cost savings.
Variable Frequency Drives at County Pools:Audit Results 111
Audit Recommendations
The Department of Park& Recreation has been proactive in installing three VFDs (one of which
has since failed due to storing of corrosive materials in the vicinity) resulting in a reduction in
electrical costs at those locations. However, P&R has not had program objectives for reducing
costs since Fiscal Year 2012-2013 and has not installed VFDs at any of the remaining seven
pools. By installing these VFDs, we estimate the County could annually save approximately
$122,578 in electricity costs. Furthermore, the County should recoup installation costs within the
first three years. After this point, all electrical cost savings are in favor of the County.
The following recommendations address each of these areas:
Develop Program Measures
We recommend that the Department of Parks & Recreation reinstate its previous
program measures related to reduction of utility costs at all facilities by implementing
green technologies and proactive practices, or at a minimum, develop a new program
measure that addresses reduction of cost and/or energy savings.
Plan and Budget for Installing Additional VFDs
We recommend that the Department of Parks & Recreation, Aquatics Division, develop
and implement a written plan for installing VFDs at all County operated swimming pools.
Then incorporate the plan into future fiscal years' budget that will reflect the installation
of VFDs and reduction of electricity expenditures.
Variable Frequency Drives at County Pools:Audit Recommendations 112
Management's Comments
/
William P.kenoi
Clayton S.Houma
Director
Mayor
Kenneth J.Van Bergen
Deputy Diredar
Countp of itiatuat
DEPARTMENT OF PARKS AND RECREATION
101 Paulo'Wert.••u ice 6•Hilo.Hirano 961'20
MOS)961-8311 •Fax OOP%I-MD
December 4.2015
Ms. Bonnie S.Nims, Legislative Auditor
County of Ilawaii
Office of the Legislative Auditor
1266 tablet Avenue.Suite A.8
Hilo Hawaii 96720
Subject: Performance Audit - Variable Frequency Drives at P&R Six Miming Pools
Dear Ms, Nims,
In an effort to provide cost savings at our swimming pools.,the Department of Parks and
Recreation began taking proactive cost savings musses by installing our first of three variable
frequency drive(VFD)unit in 2006, We appreciate you and your stalls efforts in working
collaboratively with personnel from our department to evaluate the cost effectiveness of
installing these VFDs and providing us this performance audit.
The Department of Parks and Recreation generally agrees with the findings of this audit. The
Department ill be reinstating program objectives to reduce utility costs at our swimming pools.
We are currently in the process of procuring a VII)unit at Kona Community Aquatic Center.
This VDF unit will be able to operate the two pumps at the. pool and is expected to provide
substantial energy Gist savings.
We will revisit and establish a plan for installing VFD units at our remaining pools. However,
some pools are feasible for installation whik certain pools arc in need of major improvements
and upgrades, With ow current on-going projects,we do not have enough projects managers to
properly oversee installation of VFDs in which a complete overhaul of the pool is needed.
The Department recognizes the potential energy savings by installing V Ds in our remaining
pools. With the results of this audit verifying the cost savings and return on investment,we look
forward to utilizing this audit as a tool to obtain VFD funding in our future budgets
Sincerely.
63f1"fio
Clayton Vlonma
Director
coupfy Harael 4 tai Enoid ofoir'uobtr°fwd.,ard E"Pitir.."
Variable Frequency Drives at County Pools: Management's Comments 113
Appendix A: Audit Criteria
County of Hawaii, Part I Volume II, the Proposed Operating Budget, FY 2012-2013 (March
1, 2012) describes the Department of Parks & Recreation Aquatics program objectives:
11. Reduce utility costs at all facilities by implementing green technologies and proactive
practices.
12. Reduce chemical costs at all facilities by prudent work practices, education and new
technologies.
"Countywide Swimming Pools Assessment and Repairs—September 2007" consultant
report by Okahara &Associates (September 27, 2007) contained recommendations for five
County-owned swimming pools which needed repairs, existing pumps needed to be replaced
and in addition, installing VFDs in each pool. The full report is maintained with P&R
Administration, Parks Planning Division.
Variable Frequency Drives Help Pools Maximize Energy Efficiency by Emily Attwood,
(Athletic Business, April 2012) (http://www.athleticbusiness.com) describes the advantages of
using a VFD and states in part:
"People are looking for anything they can do to decrease operating costs, and one of the
big ways they can make an impact is to save electricity," says Robert Kappel, executive
board chair of the Professional Pool Operators of America. "And one of the best-kept
secrets in the industry is variable frequency drives."...
The process takes advantage of the affinity law, says Association of Pool and Spa
Professionals technical committee chair Steve Barnes. For example, if a pump that turns
1,000 RPM at full speed moves 1,000 gallons per minute, when the speed is reduced to
500 RPM, it moves 500 gallons per minute. "The flow rate is proportional to the speed of
the motor," explains Barnes. "But when you cut the speed in half, the pressure drops to
one quarter. More importantly, the power drops to one eighth. So there's this huge
decrease in energy use on the same pump running at half speed. To turn over the pool,
you have to run it twice as long, but even running the pump twice as long, you're only
using a quarter of the electricity."...
Pools that operate year-round can potentially recoup the cost of a VFD in less than a
year, and though the payoff may take longer for a seasonal pool, the savings are, more
often than not, still worth the investment...
Energy efficiency is already on the legislative agenda in states like California, Florida
and Arizona, though laws are aimed mostly at residential pools, which have even greater
potential for energy savings. But both Barnes and Kappel believe that it won't be very
Variable Frequency Drives at County Pools::Audit Criteria 114
long before the industry tackles energy use in commercial pools. Even so, with the
savings pool operators stand to gain, there's no reason to wait until energy reform
becomes compulsory to look into improved technology. "The time is past due," says
Kappel. "If I operated a facility, I would be all over VFDs."
VFD's-how they work and can save you money(Commercial Energy Specialist (CES)
publication Water Quality News, January 20, 2008) (http://www.ceswaterqualitynews.org/)
states in part:
..The addition of a Variable Frequency Drive (VFD) to a pool pumping system can offer
dramatic potential energy savings, while protecting the motor at the same time...
VFD's match the motor speed to the desired flow.
The operating speed of a motor connected to a VFD is varied by changing the frequency
of the motor supply voltage. This is done completely automatically and without operator
involvement, allowing continuous speed and flow control. As shown above, motor-driven
systems are often designed to handle peak loads and may have an additional safety
factor. This often leads to energy inefficiency in systems that operate for extended
periods at reduced load. The ability to adjust motor speed enables closer matching of
motor output to load and often results in very large energy savings.
How much can you save using a VFD?
In these centrifugal pool pumps, (according to energy conservation experts) energy
consumption is proportional to the cube of the flow rate. In plain English that means that
even small reductions in speed and flow can result in significant energy savings. In pool
applications, significant energy and cost savings can be achieved by reducing the
operating speed when the filters are clean, or when the pool is experiencing off-peak
loads.
How great are the savings?
A motor running at 50% of full speed capacity has a motor torque of 25% of full speed. In
addition, electricity required to operate the motor at 50% of full speed is 12.5% of the
amount of electricity required if the motor was running at 100% full speed capacity.
Thus, reducing motor speed can significantly reduce the electrical energy consumption.
Therefore, a pump which is operating at 50% speed in OFF PEAK times is saving 87.5%
of energy used.
So, in a typical pool pump-room scenario where the pump is being "trimmed", it is very
common to achieve considerable peak time savings by replacing the "trimming" valve
with "reducing the speed" of the motor to achieve design flow rate. As the filter gets
soiled, the VFD will increase the flow rate to compensate for the dirty filter.
Variable Frequency Drives at County Pools:Audit Criteria 115
Most VFD installations will pay for themselves quickly, normally payback will occur within
12-18 months.
Saving Energy at the Swimming Pool with VFDs, Variable-Frequency Drives Reduce
Energy Costs and Protect Motors at South Windsor, Conn., Pool Complex by Paul Miller
(Control Global, May 5, 2008) (http://www.controlglobal.com) describes energy costs savings at
the Veterans Memorial Pool Park in South Windsor, Connecticut:
The electricity required to run these four pumps on a 24/7 basis is by far the pools
largest operational expense, and tens of thousands of dollars are budgeted for utility
costs each season. As a result, Tim Friend, plant supervisor, is constantly looking for
ways to improve efficiency and reduce costs, while still maintaining water purity.
We wanted to lower our power bills, says Friend, " We knew we were wasting energy by
always running the pumps at full power—especially after hours. There are fewer
impurities in the water when nobody is swimming, so by slowing the flow at night, we
knew we could still maintain adequate filtration in the pool and maintain the same levels
of water quality...
Variable-frequency drives help reduce energy costs
Friend then drew on his experience operating water treatment and purification plants,
where variable-frequency drives (VFDs) are often used to allow pump motors to be
safely operated at reduced speeds. To find the best solution for the pools, he consulted
with Brian Robinson, a sales engineer at FlowTech, a local sales and service
representative for ABB VFDs. Friend and Robinson had previously worked together on a
number of projects.
Brian turned me on to VFDs a long time ago," said Friend. "We saw how great they
worked in similar applications on several previous projects. By installing VFDs at the
pool, we determined that we could reduce the motor speed, but still run our system with
the valves completely open—all the while, achieving the full-flow rate we need to run the
filtration systems....
After installation, the pump speeds were set back using the on-board time clocks that
initiate pre-programmed, pre-set speeds in the VFDs. The crew programmed the pumps
to run at 90% power during open-pool hours, and to ramp down to 60% for 12 hours
each night after the pool closed. These reduced settings were expected to reduce
energy consumption by 65,000 kWh per season, a savings of more than $7,000 in
operational cost annually...
Variable Frequency Drives at County Pools:Audit Criteria 116
Two-year payback anticipated
With the energy savings the pools complex now is experiencing, Friend anticipates
recouping the entire project budget, the cost of the VFDs and their installation, in two
seasons.
We don't have the final numbers back from this season yet, but between the energy we
are saving and State of Connecticut energy grants, we're thinking the retrofit will have
paid for itself by the end of next year. This is by far the best decision we could have
made..."
Aquatic Facility Design & Optimization Pitfalls and Opportunities PowerPoint presentation
by Alvaro Mendoza of Commercial Energy Specialists (CES) (United State Swim School
Association, 2013) (http://www.usswimschools.orq) describes electrical savings of using a VFD:
• Instead of turning OFF the pump, you can turn it down with a VFD.
• Variable Frequency Drives (VFD's) are a tremendous source of energy savings
while not sacrificing pump longevity or performance.
• Major savings are expected in most applications as pool pumps are generally
oversized by design, and must be trimmed back with proportioning valves.
• Protects against surges, brownouts and other site power issues.
• In comparison to trimming pumps by adding restrictions, VFD 's work by varying
the "speed " of the motor to provide the desired flow rate.
• VFD 's also reduce the power company "Demand Charges " -the surcharge paid
by larger power customers. So you will pay less for the electricity property -wide.
• This savings is applied to your entire electric bill, not just the swimming pool or
spa portion.
• During normal operations, some pumps can be operated at 80% of peak capacity
due to more efficient piping runs, and/or oversized pumps.
✓ During this time period the electrical consumption would be .8 x .8 x .8 or
51.2% of normal power.
• During off-peak operations, some pumps could be operated at 50% of peak
capacity while still circulating, filtering, and heating.
✓ During this time period the electrical consumption would be .5 x .5 x .5 or
12.5% of normal power.
VFD Information (Commercial Aquatic Services, Inc., Watermark Energy Reduction)
(http://www.swimcas.com/) provides information on cost savings using VFDs:
Variable Frequency Drives at County Pools:Audit Criteria 117
We reduce the high energy consumption of pool filtration systems by controlling water
flow using VFD, timer/controller, and electrical bypass system. A simple 20% reduction
to water flow will yield more than 50% in electrical savings.
Your system does not need to run at 100% capacity all the time. By utilizing proven and
reliable technology to vastly improve existing motor/pump/filter system efficiency, while
maintaining the highest water quality, you can reduce electric cost by 66%to 33%.
Case study I
Southern California High School
Competition Pool: 486,000 Gallons
Before the VFD was installed, the pool was warm, clean and clear with excellent water
quality. Cost to run the motors: $29,381 per year. After the VFD was installed, the pool
was warm, clean and clear with excellent water quality. Cost to run the motors: $11,160
per year. Electric bill reduced by 62%
Before VFD installation: After VFD installation:
The 40HP (25.8KW) The same motor now runs at
motor ran at 100% 11.6 KW for 16 hrs and
i.e., 24 hrs day. 6.2 KW for 8 hrs every day, all
365 days year. = 226,008 year. = 85,848
KWH/year KWH/year
(13 cents per KWH) = $29,381/year (13 cents per KWH) = $11,160/year
Resulting in an annual saving of$18,221
With power utility incentive, payback was less than months!
Case study II
Foothills YMCA: 128,000 Gal pool, 10HP motor, Power use before VFD system: 87,796
KWH, power use after VFD system: 32,149 KWH. Total annual savings: $6,844 with
63% energy reduction.
Case study Ill
Cal State University Pool: 287,000 Gal pool, power use before VFD system: 155,490
KWH, power use after VFD system: 82,004 KWH. Total annual savings: $9,553 with
47% energy reduction.
Case study IV
Beach City Fitness Pool: 787,000 Gal competition pool, power use before VFD system:
346,896 KWH, power use after VFD system: 209,418. Total annual savings: $27,222
with 40% energy reduction.
Variable Frequency Drives at County Pools:Audit Criteria 118
Appendix B: Detailed Pool Electricity Costs
Below is the detailed information for each of the three County-owned pools with VFDs:
• Kawamoto Swim Stadium
Prior to installing the VFD, from March to June 2006, electricity cost for four months
totaled $35,664 or an average per month of$8,916. After VFD installed, electricity cost
for four-month total was $13,116 or an average per month of$3,279. The difference
between the per month averages was $5,637 for a 63 percent decrease in electricity.
This substantial decrease is due, in part, to the fact that the pool is covered and not as
exposed to the elements.
KAWAMOTO SWIM STADIUM
$10,000.00
$9,000.00
$8,000.00
$7,000.00
$6,000.00
$5,000.00
$4,000.00
$3,000.00
$2,000.00
$1,000.00
$0.00
Mar'06 Apr'06 May'06 June'06 Sept'07 Oct'07 Nov'07 Dec'07
Kawamoto Swim Stadium electricity cost before and after VFD.
VFD in use from: September 2007 to December 2007 (first four months)
Source: County of Hawaii P&R -Aquatics.
• Laupahoehoe Swimming Pool
Prior to installing the VFD, from May to August 2008, electricity cost for four months
totaled $14,197 or an average per month of$3,549. After the VFD installed, electricity
cost for four-month total was $8,169 or an average per month of$2,042. The difference
between the per month averages was $1,507 for a 42 percent decrease in electricity
cost.
Variable Frequency Drives at County Pools: Detailed Pool Electricity Costs 119
LAUPAHOEHOE SWIMMING POOL
$4,000.00
$3,500.00
$3,000.00
$2,500.00
$2,000.00
$1,500.00
$1,000.00
$500.00
$0.00
May'08 June'08 July'08 Aug'08 May'09 June'09 July'09 Aug'09
Laupahoehoe Swimming Pool electricity cost before and after VFD.
VFD in use from: May 2009 to August 2009 (first four months)
Source: County of Hawaii P&R -Aquatics.
• Pahoa Community Aquatic Center (PCAC)
Prior to installing from February to May 2013, the electricity cost for four months was
$37,005 or an average of$9,251 and after installation was $28,594 or an average of
$7,148. The difference between both per month averages was $2,103 for a decrease
of 23 percent in electricity cost.
PAHOA COMMNITY AQUATIC CENTER
$12,000.00
$10,000.00
$8,000.00
$6,000.00
$4,000.00
$2,000.00
$0.00
Feb'13 Mar'13 Apr'13 May'13 Sept'13 Oct'13 Nov'13 Dec'13
Pahoa Community Aquatic Center electricity cost before and after VFD.
VFD in use from: September 2013 to December 2013 (first four months)
Source: County of Hawaii P&R -Aquatics.
Variable Frequency Drives at County Pools: Detailed Pool Electricity Costs 120