HomeMy WebLinkAboutBLG_BLD-23-001_-_2018_IRC_Table_R802.11BLD-23-001 2018 IRC Table R802.11 Revised to Accommodate Rafters with Longer Cantilevers The following three tables on the following page have been generated to address the need for rafter-to-top plate connection uplift values for rafters that have a roof overhang greater than 2 feet but not exceeding 4 feet. Table R802.11 only provides information for rafters having a maximum overhang of 2 feet. Be aware that these tables are based upon the following assumptions: Roof pitch < 5:12. Where the roof pitch >/= to 5:12, the tabulated uplift values will be conservative. Exposure C (or B) and a maximum 33-foot mean roof height are assumed. Rafter spacing of 24”. For rafter spacing of 48”, double the tabulated uplift values. This memo is not intended to address roof trusses. The tabulated uplift values include an allowance for roof and ceiling assembly dead load of 15 psf. Linear interpolation between tabulated roof spans and wind speeds shall be permitted. The intent of this memo is to provide a prescriptive solution for 2018 IRC Section R802.11.1.2 and thus these tables may be utilized for selecting the appropriate uplift connector without the need for engineering calculations. V ult=120 mph Exposure C Roof pitch < 5:12  Rafter Spacing = 24”  Uplift <lbs.> Overhang <ft.>  Roof Span <ft.> 2 3 4  24 400 465 529  28 450 512 573  32 498 559 620  36 548 607 666  42 624 680 738  48 698 753 810   V ult=130 mph Exposure C Roof pitch < 5:12  Rafter Spacing = 24”  Uplift <lbs.> Overhang <ft.>  Roof Span <ft.> 2 3 4  24 512 600 682  28 578 660 739  32 642 721 800  36 706 783 859  42 804 876 951  48 900 971 1044   V ult=140 mph Exposure C Roof pitch < 5:12  Rafter Spacing = 24”  Uplift <lbs.> Overhang <ft.>  Roof Span <ft.> 2 3 4  24 634 746 848  28 716 821 920  32 796 897 994  36 876 974 1069  42 998 1091 1183  48 1120 1208 1300