HomeMy WebLinkAboutRemaining Useful Life Report- Country Club Condo-Hotel
Final Report
June 2014
Remaining Useful Life Determination
for the
Country Club Condominium/Hotel
Hilo, Hawaii
TMK: (3) 2-1-005: 020
Submitted By
SSFM INTERNATIONAL, INC.
Project Managers, Planners, & Engineers
99 Aupuni Street, Suite 202
Hilo, Hawaii 96720
Phone: (808) 933-2727
Fax: (808) 521-7348
Email: rishisaka@ssfm.com
Page 1
Statement of SSFM International, Inc.’s Quality Process
It is the policy of SSFM to have a consistent and systematic approach to the development and
review of its reports and other project deliverables.
All projects and products of our service are subject to a quality process and in no case will the
quality review be eliminated. The main purpose of this process is to assure:
Clarity, completeness, coordination, and accuracy of documents.
That the project, study or investigation meets the Client's objectives.
That the requirements of our Agreement with the Client have been met, and the Client
has received the value of the fee to be paid.
The Preparation of This Report Was The
Responsibility of and Completed By:
____________________________________ ____________
signature date
The Quality Review of This Report Was The
Responsibility of and Completed By:
____________________________________ ____________
signature date
6/10/2014
6/12/2014
Page 2
I. Scope of Work
The scope of work is to estimate the Remaining Useful Life (RUL) of the Building Facilities and
Physical Plant for the Country Club Condominium Hotel. This report is intended to be used as
part of decision making on the future utilization of this property.
The Study was based on the examination of the property through meetings, interviews and on-
site inspections by a team of experienced and knowledgeable professionals.
Location and Vicinity Maps, along with aerial views of the property are provided in Appendix A.
Country Club Condominium and Hotel located at 121 Banyan Drive, Hilo, Hawai‘i.
II. Existing Conditions
This Property is currently being used as Condominium/Hotel. It is a six (6) story concrete and
masonry structure, which includes the lobby/office area on the front lower level section and a
restaurant-bar section currently not in use. The ground floor level under the rear section of the
building is utilized as parking.
Page 3
The current lease will expire on March 14, 2015. The future use of this property and potential
terms and conditions for lease renegotiations will be determined as part of the process with the
Hawaii State Department of Land and Natural Resources.
BACKGROUND INFORMATION :
· Name of Property: COUNTRY CLUB CONDOMINIUM HOTEL
· Address: 121 Banyan Drive, Hilo, HI 96720
· TMK of Property: 3-2-1-005:020
· Leased Agreement Info: No. 3269
o Lessee: COUNTRY CLUB-HAWAI’I INC. TRUST
o Duration: Expires on March 14, 2015
· General Description of Property:
o Number of Buildings: One (1) Six Story Building.
o Type of Construction: Cast in Place Concrete and Concrete Masonry
o Year Constructed: 1969
· Grounds Information:
o Pavement & Parking: Asphaltic Concrete
o Walkways: Concrete
o Miscellaneous: Swimming Pool & Grounds Areas
· Utility Type & Construction:
o Electrical: Typical Pre-Current Building Code; In need of upgrading
o Plumbing: Cast Iron, Copper & PVC
o Air Conditioning: 60 ton Trane Chilled Water Unit with Individual In-Room Air
Handling Units
· Miscellaneous:
o Elevators: Two (2), one at the front and another at the rear of this structure.
III. Site Visit
On March 4, 2014, a site visit was performed by a civil engineer, a structural engineer, a
mechanical engineer, an electrical engineer and Mr. Kevin Aoki, Condominium/Hotel Operator,
to assess the general condition of the buildings and physical plant components of the Country
Club Condominium Hotel.
An interview was first conducted with Mr. Aoki to discuss the history of the property
improvements, as well as to gain insight on recent repairs and known issues. After the interview,
the site visit and evaluation inspection was performed during which the major building and
physical plant components were evaluated.
The condition of the major components observed is documented in Appendix B.
Page 4
IV. Discussion
The structural, electrical and mechanical elements are the most important factors in determining
the RUL. The condition of major equipment related to these systems, such as air conditioning
equipment, large capacity water heaters, transformers, electrical service components, etc. are also
considered, but have less of an impact since they can be replaced with minimal disruption to the
use of the building. Items such as furnishings are not considered to impact the RUL. Isolated
conditions, including but not limited to the roofing membrane, corrosion of the steel staircase
and air conditioning chiller unit, may require repair or replacement to achieve the RUL, but this
can be achieved without significantly impacting the current operations and usage of the facility.
The primary objective was to inspect and examine the elements of the building structure and
physical plant, including the grounds, which are controlling elements in determining the RUL in
terms of a range of years.
Significant Findings are itemized below (See Appendix B for Element Numbers):
· Element No. S 6.a – Steel Stairways were observed with significant rust throughout.
· Element No. E 1 – Electrical System, Wiring & Breakers are out dated. Continued use
will require the upgrade of this system to meet current codes.
· Element No. M 1.a & 2.a – Air Conditioning Water Chiller & the Exhaust Fan System
were unsatisfactory and not fully functional. Although not a critical element to RUL,
replacement of this element would be required with continued use.
· Element No. U 2.a – Boiler System is old and obsolete. Remaining useful life for this
would be 2-5 years. Although not a critical element to RUL, replacement of this element
would be required with continued use.
In addition, we note the items disclosed as part of the Pre-Inspection Meeting w/ the Lessee and
our own visual inspection.
· No noticeable settlement, erosion nor drainage-flooding has occurred.
· There is evidence of Concrete Spalling in various locations including floor slabs, walls,
columns and beams. None of which were considered serious and should be repaired with
continued use.
· The roof is cast in place concrete and there is evidence of leaking and is in need of re-
application of roofing. Roofing is under warranty but the building maintenance
supervisor is having trouble getting them to perform the corrective work.
· Plumbing has been operational with no significant problems with exception of normal
preventative and repair maintenance.
· Electrical Source by HELCO is satisfactory. The original transformer has been replaced,
however, it has not been removed due to its large size.
· Water and Wastewater by the County of Hawaii have performed satisfactorily with no
significant disruptions.
· The facility is partially compliant with ADA requirements. Continued use would require
an assessment of this element to current standards.
· Elevators were in satisfactory condition. Both elevators are under maintenance contract
with Otis Elevators.
Page 5
V. Conclusion
Based on the documentation available, meeting with the Lessee and the Site
Evaluation/Inspection performed on March 4, 2014, the Remaining Useful Life (RUL) is
determined to be 5 - 8 years assuming the current usage is continued. This RUL is based on
deficiencies noted on non-structural elements because, in this Building Physical Plant, the non-
structural elements are considered controlling parameters.
VI. Conditions and Limitations
The scope of work is limited to general visual observation of accessible major structural,
architectural, mechanical, electrical, plumbing and sewer components of the facility in order to
estimate remaining useful life of the facility. This Evaluation and Inspection was prepared based
on examination of available records, interview meetings w/ the Lessee and visual on-site
inspection of the Physical Plant & its operation.
This report does not address any furnishings or non-permanent equipment. We have not verified
the structural integrity of all members to support present or code required gravity or lateral loads,
or performed any testing of the various building components. We did not perform any testing or
investigations to confirm the accuracy of any drawings, calculations or documentation provided
for review as a part of this evaluation. It is beyond the scope of this report to determine what
deficiencies would need to be remediated in order to bring the current facility up to code. This
report does not address any other portions or aspects of the existing facility other than those areas
mentioned, nor does it provide warranty, either expressed or implied, for any portion of the
existing facility.
Remaining Useful Life is the duration for which the facilities will be useful to the business, not
how long they will actually last. It is based on many factors and can change over time depending
on factors such as improvements made to the property, economic changes and changes to
laws. The remaining useful life estimates, assume basic maintenance and isolated critical
repairs. The facilities may remain functional past these estimated spans, however, it is expected
that widespread, more costly repairs and upgrades would begin to compound and it may no
longer be feasible to operate at the status quo.
VII. Personal Background
HUGH Y. ONO. P.E.
Hugh Ono is a Civil Engineer with background in Construction, Construction Management,
Engineering Management and Administration and Building & Grounds Maintenance
Management.
Page 6
RENEE ISHISAKA, P.E.
Renee Ishisaka is a Structural Engineer with over 5 years of experience in a wide variety of both
design and construction projects. Projects have involved reinforced, prestressed and post-
tensioned concrete; structural steel; masonry; and timber construction. Ms. Ishisaka has
experience with the following types of projects: Hospitals, Department of Defense projects,
airport facilities, commercial/office buildings, residential buildings, educational facilities, and
hotels.
NIMR TAMIMI, P.E.
Nimr Y. Tamimi, P.E., LEED AP, is a Principal at Engineering Partners Inc. with 26 years of
experience as a design mechanical engineer in Hawaii. Mr. Tamimi’s experience relevant to this
project include the design of new mechanical systems and renovations of existing systems for
Hotels, Resorts, Multifamily residential, restaurants, swimming pools, domestic water heating
systems, fuel gas distribution systems, and HVAC systems. Included as part of those projects are
payback analysis, usable life analysis, due diligence, and trouble shooting.
CHRISTOPHER LOVETT, P.E.
Christopher Lovett, P.E., is a Principal at Engineering Partners Inc. with over 16 years of
experience in the design, specification and construction of commercial electrical and
telecommunications systems. Mr. Lovett’s experience ranges from designing power and lighting
distribution systems for both medium and low voltages and telecommunications infrastructure
design. Projects include extensive Electrical Engineering designs for hotels/casinos, high-rise
residential, hospital, educational facilities and commercial/office buildings. Mr. Lovett provides
extensive experience in project management, construction administration, scheduling and cost
estimating.
Appendix A
Figure 1: Location Map
(Images from Google Earth)
Not to Scale
Project Location
Figure 2: Vicinity Map
(Images from Google Earth)
Not to Scale
Reed's Bay
Hotel
Country Club
Condominium HotelUncle Billy's Hilo
Bay Hotel
Kamehameha Avenue
N
Prepared for : State of Hawaii Department of Land and Natural Resources
Aerial Views of Country Club Condominium Hotel
View from South
View from West
View from North
View from East
Appendix B
El
e
m
e
n
t
C
o
d
e
s
:
G
-
G
r
o
u
n
d
s
;
S
-
S
t
r
u
c
t
u
r
a
l
,
P
-
P
l
u
m
b
i
n
g
,
M
-
M
e
c
h
a
n
i
c
a
l
,
U
-
U
t
i
l
i
t
y
,
O
-
O
t
h
e
r
/
M
i
s
c
.
Photos Referenced:
G1
G
r
o
u
n
d
s
-
S
e
t
t
l
e
m
e
n
t
&
E
r
o
s
i
o
n
a
.
S
o
m
e
e
r
o
s
i
o
n
c
a
u
s
e
d
b
y
h
i
g
h
s
u
r
f
&
w
a
v
e
a
c
t
i
o
n
a
t
o
n
e
t
i
m
e
a
.
N
o
t
c
o
n
s
i
d
e
r
e
d
s
i
g
n
i
f
i
c
a
n
t
3
N
/
A
N
/
A
N
/
A
N
/
A
N
/
A
G2
G
r
o
u
n
d
s
-
D
r
a
i
n
a
g
e
&
R
u
n
o
f
f
a
.
P
a
r
k
i
n
g
a
r
e
a
i
n
r
e
a
r
o
f
b
u
i
l
d
i
n
g
a.
M
i
n
o
r
P
o
n
d
i
n
g
n
o
t
e
d
.
2
4
5
2
5
1
0
a
.
I
M
G
_
2
4
5
3
N
/
A
G3
G
r
o
u
n
d
s
-
P
a
r
k
i
n
g
&
P
a
v
e
d
A
r
e
a
s
a.
D
r
i
v
e
w
a
y
i
n
t
o
p
r
o
p
e
r
t
y
i
s
a
s
e
p
a
r
a
t
e
p
a
r
c
e
l
b.
D
r
o
p
o
f
f
/
p
a
r
k
i
n
g
a
r
e
a
i
n
f
r
o
n
t
o
f
R
e
s
t
a
u
r
a
n
t
/
L
o
b
b
y
c.
P
a
r
k
i
n
g
a
r
e
a
b
e
h
i
n
d
/
b
e
n
e
a
t
h
b
u
i
l
d
i
n
g
a.
A
C
P
a
v
e
m
e
n
t
i
s
f
a
i
l
i
n
g
i
n
s
o
m
e
l
o
c
a
t
i
o
n
s
.
S
u
r
f
a
c
e
i
s
cr
a
c
k
e
d
a
n
d
w
o
r
n
.
b.
S
e
v
e
r
e
p
o
t
h
o
l
e
s
a
t
e
n
t
r
a
n
c
e
t
o
d
r
o
p
o
f
f
a
r
e
a
.
c.
A
C
P
a
v
e
m
e
n
t
e
x
h
i
b
i
t
s
m
i
n
o
r
c
r
a
c
k
i
n
g
a
n
d
w
e
a
r
.
Ho
w
e
v
e
r
,
p
a
v
e
m
e
n
t
f
a
i
l
u
r
e
w
a
s
n
o
t
o
b
s
e
r
v
e
d
.
2 2 2
45
25 5 10 5a. IMG_2445 b. See IMG_2453 c. IMG_2447a. Resurfacing is recommended with continued use, however, since this is a separate parcel, there is no control over its condition.b. Resurfacing or patching is recommended with continued use.
S1
S
t
r
u
c
t
u
r
a
l
-
F
o
u
n
d
a
t
i
o
n
N
O
T
A
C
C
E
S
S
I
B
L
E
NO
S
I
G
N
I
F
I
C
A
N
T
F
I
N
D
I
N
G
S
O
F
S
E
T
T
L
E
M
E
N
T
N
O
R
MO
V
E
M
E
N
T
.
1
4
5
2
5
2
5
N
/
A
N
/
A
S2
S
t
r
u
c
t
u
r
a
l
-
F
l
o
o
r
S
l
a
b
s
a.
V
a
r
i
o
u
s
l
o
c
a
t
i
o
n
s
b.
L
e
d
g
e
r
a
t
E
l
e
v
a
t
o
r
S
h
a
f
t
a.
S
p
a
l
l
i
n
g
a
t
v
a
r
i
o
u
s
l
o
c
a
t
i
o
n
s
n
o
t
e
d
.
b.
R
u
s
t
i
n
g
a
n
d
l
o
o
s
e
/
m
i
s
s
i
n
g
b
o
l
t
s
o
b
s
e
r
v
e
d
a
t
l
e
d
g
e
r
s
.
1
4
5
2
5
1
5
a. IMG_2494 b. IMG_2507a,b. Recommend repairs with continued use.
S3
S
t
r
u
c
t
u
r
a
l
-
W
a
l
l
s
a.
V
a
r
i
o
u
s
l
o
c
a
t
i
o
n
s
i
n
c
l
u
d
i
n
g
e
x
t
e
r
i
o
r
w
a
l
l
s
(
e
s
p
e
c
i
a
l
l
y
n
e
a
r
w
i
n
d
o
w
s
)
,
In
t
e
r
i
o
r
a
n
d
E
x
t
e
r
i
o
r
E
l
e
v
a
t
o
r
R
o
o
m
W
a
l
l
s
a
n
d
S
t
a
i
r
w
e
l
l
W
a
l
l
s
a.
C
r
a
c
k
i
n
g
a
n
d
S
p
a
l
l
i
n
g
a
t
v
a
r
i
o
u
s
l
o
c
a
t
i
o
n
s
n
o
t
e
d
1
4
5
2
5
1
5
a. IMG_2523, IMG_2491a. Recommend repairs with continued use.
S4
S
t
r
u
c
t
u
r
a
l
-
C
o
l
u
m
n
s
&
B
e
a
m
s
a.
V
a
r
i
o
u
s
L
o
c
a
t
i
o
n
s
a.
S
p
a
l
l
i
n
g
n
o
t
e
d
a
t
t
h
e
u
p
p
e
r
l
i
m
i
t
s
o
f
C
o
n
c
r
e
t
e
C
o
l
u
m
n
s
.
1
45
25 10 N/Aa. Recommend repairs with continued use.
S5
S
t
r
u
c
t
u
r
a
l
-
R
o
o
f
F
r
a
m
i
n
g
a.
R
e
i
n
f
o
r
c
e
d
C
a
s
t
i
n
P
l
a
c
e
C
o
n
c
r
e
t
e
R
o
o
f
b.
R
o
o
f
i
n
g
T
r
e
a
t
m
e
n
t
a.
C
r
a
c
k
i
n
g
a
n
d
e
f
f
l
o
r
e
s
e
n
c
e
d
u
e
t
o
w
a
t
e
r
i
n
f
i
l
t
r
a
t
i
o
n
ob
s
e
r
v
e
d
.
b.
E
v
i
d
e
n
c
e
o
f
l
e
a
k
a
g
e
a
n
d
w
a
t
e
r
d
a
m
a
g
e
o
b
s
e
r
v
e
d
i
n
so
m
e
l
o
c
a
t
i
o
n
s
.
R
o
o
f
i
n
g
t
r
e
a
t
m
e
n
t
i
s
t
o
r
n
i
n
p
l
a
c
e
s
a
n
d
po
n
d
i
n
g
o
f
w
a
t
e
r
w
a
s
o
b
s
e
r
v
e
d
.
1
45
Un
k
n
o
w
n
2
5
1
0
a. IMG_2519 b. DSCN0465a. Recommend repairs with continued use.b. In need of re-application of roofing.
S6
S
t
r
u
c
t
u
r
a
l
-
S
t
a
i
r
s
a
.
S
t
e
e
l
S
t
a
i
r
w
a
y
s
a.
W
i
d
e
s
p
r
e
a
d
R
u
s
t
i
n
g
o
b
s
e
r
v
e
d
.
2
4
5
2
0
8
a. DSCN0471, DSCN0481a. Replacement or Repair necessary.
S7
S
t
r
u
c
t
u
r
a
l
-
B
a
l
c
o
n
i
e
s
a
.
T
y
p
i
c
a
l
B
a
l
c
o
n
y
-
A
l
l
R
o
o
m
s
No
s
i
g
n
i
f
i
c
a
n
t
i
s
s
u
e
s
n
o
t
e
d
.
2
4
5
2
0
1
0
a
.
I
M
G
-
2
5
2
2
N
/
A
P1
P
l
u
m
b
i
n
g
-
D
i
s
t
r
i
b
u
t
i
o
n
S
y
s
t
e
m
a
.
B
u
i
l
d
i
n
g
P
h
y
s
i
c
a
l
P
l
a
n
t
a.
N
o
m
a
j
o
r
p
r
o
b
l
e
m
s
o
t
h
e
r
t
h
a
n
r
o
u
t
i
n
e
r
e
p
a
i
r
a
n
d
ma
i
n
t
e
n
a
n
c
e
.
2
4
5
2
0
1
5
N
/
A
N
/
A
P2
P
l
u
m
b
i
n
g
-
W
a
s
t
e
S
y
s
t
e
m
a
.
B
u
i
l
d
i
n
g
P
h
y
s
i
c
a
l
P
l
a
n
t
a.
N
o
m
a
j
o
r
p
r
o
b
l
e
m
s
o
t
h
e
r
t
h
a
n
r
o
u
t
i
n
e
r
e
p
a
i
r
a
n
d
ma
i
n
t
e
n
a
n
c
e
.
2
4
5
2
0
1
5
N
/
A
N
/
A
E1
E
l
e
c
t
r
i
c
a
l
-
W
i
r
i
n
g
&
D
i
s
t
r
i
b
u
t
i
o
n
a.
P
a
n
e
l
o
n
e
a
c
h
f
l
o
o
r
b.
T
r
a
n
s
f
o
r
m
e
r
a.
O
p
e
r
a
t
i
o
n
a
l
w
i
t
h
i
n
L
i
m
i
t
s
.
b.
W
a
s
r
e
p
l
a
c
e
d
;
o
r
i
g
i
n
a
l
s
t
i
l
l
i
n
p
l
a
c
e
d
u
e
t
o
d
i
f
f
i
c
u
l
t
y
i
n
re
m
o
v
a
l
.
2
4
5
1
5
5
b. IMG_2451, DSCN0451a. In need of upgrade with continued use. Current system unable to accommodate surge loads.
E2
E
l
e
c
t
r
i
c
a
l
-
S
o
l
a
r
S
y
s
t
e
m
s
N
O
N
E
N
O
T
E
D
NO
T
A
P
P
L
I
C
A
B
L
E
N/
A
N
/
A
N
/
A
N
/
A
N
/
A
N
/
A
M1
M
e
c
h
a
n
i
c
a
l
-
A
i
r
C
o
n
d
i
t
i
o
n
i
n
g
P
l
a
n
t
a.
W
a
t
e
r
C
h
i
l
l
e
r
o
n
R
o
o
f
b.
F
o
r
m
e
r
R
e
s
t
a
u
r
a
n
t
a.
R
e
p
l
a
c
e
d
i
n
t
h
e
1
9
9
0
'
s
C
o
n
d
i
t
i
o
n
i
s
f
a
i
r
a
n
d
i
n
n
e
e
d
o
f
re
p
l
a
c
e
m
e
n
t
.
N
o
t
f
u
l
l
y
o
p
e
r
a
t
i
o
n
a
l
.
b.
A
i
r
C
o
n
d
i
t
i
o
n
S
y
s
t
e
m
n
o
t
i
n
u
s
e
a
n
d
u
n
s
e
r
v
i
c
e
a
b
l
e
.
2
4
0
1
5
0
a. IMG_2489 b. DSCN0457, DSCN0479, DSCN0480a. Serious Condition and in need of Repairs or Replacement.
M2
M
e
c
h
a
n
i
c
a
l
-
A
i
r
C
o
n
d
i
t
i
o
n
i
n
g
D
u
c
t
s
a
.
E
x
h
a
u
s
t
F
a
n
s
a.
I
n
p
o
o
r
c
o
n
d
i
t
i
o
n
2
4
5
2
0
2
a
.
I
M
G
_
2
4
6
9
a. Replacement needed with continued use.
U1
U
t
i
l
i
t
y
-
E
l
e
c
t
r
i
c
a
l
P
o
w
e
r
S
u
p
p
l
y
a
.
T
r
a
n
s
f
o
r
m
e
r
-
S
e
e
I
t
e
m
E
1
b
El
e
c
t
r
i
c
S
e
r
v
i
c
e
P
r
o
v
i
d
e
d
b
y
H
E
L
C
O
N
/
A
N
/
A
N
/
A
N
/
A
N
/
A
N
/
A
U2
Ut
i
l
i
t
y
-
H
e
a
t
e
r
&
F
l
u
e
,
C
o
m
m
e
r
c
i
a
l
Siz
e
a.
B
o
i
l
e
r
/
W
a
t
e
r
H
e
a
t
e
r
a.
O
l
d
&
O
b
s
o
l
e
t
e
2
N
/
A
1
5
2
a
.
D
S
C
N
0
4
6
1
a. Boiler needs replacement.
U3
U
t
i
l
i
t
y
-
W
a
s
t
e
w
a
t
e
r
S
y
s
t
e
m
a
.
B
u
i
l
d
i
n
g
P
h
y
s
i
c
a
l
P
l
a
n
t
Pr
o
v
i
d
e
d
b
y
C
O
H
W
a
s
t
e
w
a
t
e
r
2
N
/
A
N
/
A
N
/
A
N
/
A
a. No Major problems other than routine repair and maintenance.
U4
U
t
i
l
i
t
y
-
W
a
t
e
r
S
u
p
p
l
y
S
y
s
t
e
m
a
.
B
u
i
l
d
i
n
g
P
h
y
s
i
c
a
l
P
l
a
n
t
Pr
o
v
i
d
e
d
b
y
C
O
H
D
W
S
2
N
/
A
N
/
A
N
/
A
N
/
A
a. No Major problems other than routine repair and maintenance.
U5
U
t
i
l
i
t
y
-
G
a
s
S
u
p
p
l
y
S
y
s
t
e
m
a
.
B
o
i
l
e
r
/
W
a
t
e
r
H
e
a
t
e
r
-
S
e
e
I
t
e
m
U
2
S
e
r
v
i
c
e
p
r
o
v
i
d
e
d
b
y
T
h
e
G
a
s
C
o
m
p
a
n
y
2
N
/
A
N
/
A
N
/
A
N
/
A
N
/
A
O1
A
D
A
C
O
M
P
L
I
A
N
T
a
.
B
u
i
l
d
i
n
g
P
h
y
s
i
c
a
l
P
l
a
n
t
a.
P
r
o
p
e
r
t
y
i
s
n
o
t
i
n
c
o
m
p
l
i
a
n
c
e
w
i
t
h
A
D
A
S
t
a
n
d
a
r
d
s
1
N
/
A
N
/
A
N
/
A
N
/
A
Continued use would need ADA Improvements.
O2
E
L
E
V
A
T
O
R
S
Y
S
T
E
M
2
E
l
e
v
a
t
o
r
s
o
n
e
f
r
o
n
t
;
o
t
h
e
r
r
e
a
r
Bo
t
h
i
n
g
o
o
d
c
o
n
d
i
t
i
o
n
a
s
m
a
i
n
t
a
i
n
e
d
b
y
O
T
I
S
.
3
45
15 15 IMG_2461 N/A
O3
F
i
r
e
P
r
o
t
e
c
t
i
o
n
a.
N
o
S
p
r
i
n
k
l
e
r
S
y
s
t
e
m
i
n
p
l
a
c
e
b.
F
i
r
e
A
l
a
r
m
S
y
s
t
e
m
a.
N
o
t
A
p
p
l
i
c
a
b
l
e
b.
O
p
e
r
a
t
i
o
n
a
l
2
N
/
A
N/A 10N/A 10N/A b. IMG_2463, IMG_2450N/A
O4
S
w
i
m
m
i
n
g
P
o
o
l
a.
M
a
k
a
i
o
f
B
u
i
l
d
i
n
g
n
e
x
t
t
o
O
c
e
a
n
a.
I
n
u
s
e
a
n
d
n
o
s
i
g
n
i
f
i
c
a
n
t
p
r
o
b
l
e
m
s
.
3
45
15 15 a. IMG_2524 N/A
N/
A CD CDCFN/
A D N/
A
N/
A
N/
ACCN/
A F D BD C D B DDCC
EV
A
L
U
A
T
I
O
N
S
I
T
E
I
N
S
P
E
C
T
I
O
N
T
E
A
M
:
*
S
S
F
M
I
N
T
E
R
N
A
T
I
O
N
A
L
-
H
u
g
h
O
n
o
,
P
.
E
.
&
R
e
n
e
e
I
s
h
i
s
a
k
a
,
P
.
E
.
*
C
O
U
N
T
R
Y
C
L
U
B
C
O
N
D
O
M
I
N
I
U
M
H
O
T
E
L
-
M
r
.
K
e
v
i
n
A
o
k
i
,
F
o
r
m
e
r
C
o
n
d
o
m
i
n
i
u
m
M
a
n
a
g
i
n
g
A
g
e
n
t
*
E
N
G
I
N
E
E
R
I
N
G
P
A
R
T
N
E
R
S
,
I
N
C
.
-
N
i
m
r
T
a
m
i
m
i
,
P
.
E
.
&
C
h
r
i
s
L
o
v
e
t
t
,
P
.
E
.
Pr
o
p
e
r
t
y
N
a
m
e
:
CO
U
N
T
R
Y
C
L
U
B
C
O
N
D
O
/
H
O
T
E
L
Da
t
e
:
1
0
:
3
0
a
m
,
T
u
e
s
d
a
y
,
M
a
r
c
h
4
,
2
0
1
4
N/
A C
Comments & Major Deficiencies Noted:
Es
t
i
m
a
t
e
d
A
g
e
:
I
f
Av
a
i
l
a
b
l
e
(
Y
e
a
r
s
)
RU
L
W
e
i
g
h
t
:
(1
H
i
g
h
t
o
3
L
o
w
)
De
s
c
r
i
p
t
i
o
n
o
f
F
i
n
d
i
n
g
:
El
e
m
e
n
t
Co
d
e
Remaining Useful Life (Years)Estimated Useful Life (Years)
El
e
m
e
n
t
L
o
c
a
t
i
o
n
o
f
D
e
f
i
c
i
e
n
t
E
l
e
m
e
n
t
s
N
o
t
e
d
:
Co
n
d
i
t
i
o
n
R
a
t
i
n
g
:
A
t
o
F
Country Club Condominium/Hotel – Referenced Photos
Photo 1: IMG_2453 – Parking area at rear
of building
Photo 2: IMG_2445 – Deteriorated
pavement at entry parcel
Photo 3: IMG_2447– Deteriorated
pavement at drop off area
Photo 4: IMG_2494– Concrete slab
spalling and efflorescence in stairwell
.5
Photo 5: IMG_2507 – Rusting and loose
bolt at slab ledger
Photo 6: IMG_2523– Spalling at Exterior
Wall
Photo 7: IMG_2491 – Spalling and
cracking at Elevator Room
Photo 8: IMG_2519 – Water Damage,
cracking and efflorescence at ceiling
Photo 9: DSCN0465 – Roof treatment
failure and ponding water
Photo 10: DSCN0471 – Roof stair rusting
Photo 11: DSCN0481– Typical steel stair
rusting
Photo 12: IMG_2522 – Typical Balcony
Photo 13: IMG_2451 – Electrical
transformer
Photo 14: DSCN0451- Old electrical
transformer, no longer in use
Photo 15: IMG_2489 – Air cooled chiller
unit
Photo 16: DSCN0457 – Defunct
restaurant chiller unit
Photo 17: DSCN0479 – Defunct
restaurant equipment
Photo 18: DSCN0480 – Defunct
restaurant equipment
Photo 19: IMG_2569 – Exhaust Fans Photo 20: DSCN0461 – Heater/Boiler
Room
Photo 21: IMG_2461- Elevator in Lobby Photo 22: IMG_2463 – Fire alarm pull
box
Photo 23: IMG_2450- Fire alarm control
box
Photo 24: IMG_2524 – Swimming Pool