Laserfiche WebLink
(44) Fire protection systems out of service. Section 13.1.10 is amended to read <br /> as follows: <br /> "13.1.10. The AHJ shall be verbally notified immediately when any fire <br /> protection system is out of service and on restoration of service." <br /> [2018 HSFC: 45] <br /> (45) Fire protection systems advanced notification. Sections 13.1.10.1, <br /> 13.1.10.2, and 13.1.10.3 are added to read as follows: <br /> "13.1.10.1 The county fire department shall be given a seventy-two hour <br /> notification prior to a scheduled inspection, testing, maintenance, or retesting of <br /> any fire protection system (including class I, II, and III, and combined systems, <br /> automatic fire sprinkler systems, and other fire extinguishing systems) and fire <br /> alarm systems within their respective jurisdiction in the State." <br /> [2018 HSFC: 46] <br /> "13.1.10.2 Failure to comply with the requirements of this section may result in <br /> the county fire department deeming it an invalid test. A retest may be required <br /> to be performed at the testing company's expense." [2018 HSFC: 46] <br /> "13.1.10.3 The certificate of fitness holder shall immediately notify the county <br /> fire department of any system inspection, testing or maintenance cancellations <br /> or changes to the scheduled date and time." [2018 HSFC: 46] <br /> (46) Fire protection systems inspection, testing, and maintenance labeling. <br /> Sections 13.2.3.3.1, 13.2.3.3.2, 13.2.3.3.2.1, 13.2.3.3.3, 13.2.3.3.3.1, 13.2.3.3.4, <br /> 13.2.3.3.4.1, 13.2.3.3.5, 13.2.3.3.5.1, and 13.2.3.3.5.2 are added to read as <br /> follows: <br /> "13.2.3.3.1 Inspection Label and Collar. An approved label and verification <br /> collar signifying successful passing of the system shall be provided when <br /> inspecting, testing, or maintaining any class I, II, III, and combined standpipe <br /> fire extinguishing system." [2018 HSFC: 47] <br /> "13.2.3.3.2 Five Year Inspection Label. <br /> 13.2.3.3.2.1 Class I, II, and III, and combined standpipe fire extinguishing <br /> systems passing a five-year inspection (annual inspection for class II hoses) shall <br /> have an approved, weatherproof, inspection label affixed to the fire department <br /> connection. If the system does not have a fire department connection, labels <br /> 15 <br />