My WebLink
|
Help
|
About
|
Sign Out
Home
ORD 2023-008 2022-2024
ClerkCouncil
>
Council Records
>
Ordinances
>
2023
>
ORD 2023-008 2022-2024
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/18/2023 9:46:54 AM
Creation date
1/18/2023 9:45:58 AM
Metadata
Fields
Template:
Ordinances
Ordinances - Type
ORD
Ordinances - Council Term
2022-2024
Year
2023
Ordinance
08
Effective Date
1/13/2023
Document Relationships
BIL 221 Draft 03 2020-2022
(Related)
Path:
\Council Records\Bills\2020-2022
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
46
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
shall be affixed to hose cabinets located on the ground floor and the top-most <br /> floor. <br /> (1) The label shall indicate the type of system, month and year the system was <br /> inspected, tested, and maintained; the certificate of fitness holder's name <br /> and certificate number; and the company name, address, and contact <br /> information. <br /> (2) The label shall be yellow, at least two and one-fourth inches in width and <br /> three and one-fourth of an inch in length, and clearly visible without <br /> obstructing the operation of the fire extinguishing system. <br /> (3) The label shall be constructed of a durable material approved by the AHJ. <br /> (4) The label shall be punched with no more than one year and one month." <br /> [2018 HSFC: 47] <br /> "13.2.3.3.3 Verification Service Collar. <br /> 13.2.3.3.3.1 The verification of service collar shall be a circular, solid of <br /> continuous plastic with at least a three inch diameter hole in the center and <br /> shall slide onto each hose length approximately midway from the male and <br /> female couplings after the physical inspection has been completed and deemed <br /> satisfactory. The verification service collar shall: <br /> (1) Indicate the month and year the hose was inspected; the certificate of <br /> fitness holder's name and number; and company name, address and contact <br /> information; and <br /> (2) Be constructed of other suitable materials when approved by the AHJ." <br /> [2018 HSFC: 47] <br /> "13.2.3.3.4 Inoperable System Sign. <br /> 13.2.3.3.4.1 Systems that cannot be utilized for firefighting operations shall <br /> have an inoperable system sign affixed to the fire department connection. <br /> (1) The sign shall have a white background with red lettering and be <br /> constructed of wood, metal, or plastic. <br /> (2) The letters shall be a minimum height of three inches and a minimum <br /> width of one-fourth of an inch stroke. <br /> (3) If the system does not have a fire department connection, inoperable system <br /> signs shall be affixed to hose cabinets located on the ground floor and the <br /> top-most floor. <br /> (4) The sign shall remain in place until all repairs have been made and a <br /> satisfactory system test is completed." <br /> [2018 HSFC: 47] <br /> 16 <br />
The URL can be used to link to this page
Your browser does not support the video tag.