Laserfiche WebLink
<br /> <br /> <br /> <br /> <br /> CURRENT INSPECTION <br /> <br /> 1. Maintenance: Check either: No. of: <br /> <br /> Preventive Maintenance: x Current - Backlogged <br /> Corrective Maintenance: x Satisfactory - Excessive <br /> Major (or all) items requiring repair/replacement: <br /> <br /> None. <br /> <br /> 2. Reuse: <br /> The facility has a DOH approved effluent irrigation plan: <br /> Yes No x Not applicable <br /> <br /> 3. NPDES or Chapter 62 violations (effluent limitations, spills, etc.): <br /> <br /> None <br /> 4. Visual quality of effluent on date of inspection (inspector's judgment): <br /> <br /> The effluent was noted to be clear on the date of the inspection. <br /> <br /> 5. Laboratory Data: <br /> The following influent and effluent data were collected for the period <br /> July 1997 through June 1998: <br /> <br /> a. Influent BOD5 and TSS averaged 183 mg/l and 198 mg/1, respectively. <br /> <br /> b. Effluent BOD5 averaged 2.4 mg/l and effluent TSS averaged 2.5 mg/1. <br /> 6. Facility's Present Deficiencies: <br /> <br /> 1. Excessive rust was noted on the blowers. <br /> <br /> 2. The effluent flow meter was reportedly calibrated but did not have <br /> a calibration tag. <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> O&M Report Form (12/93) 2 <br />