As amended, Table K -1 shall read:
<br /> "TABLE K -1
<br /> Location of Sewage Disposal System
<br /> •
<br /> Minimum Horizontal Distance Building Sewer Septic Tank Disposal Field Seepage Pit
<br /> In Clear Required From: or Cesspool
<br /> Buildings or structures 2 feet (610 mm) 5 feet (1,524 mm) 8 feet (2,438 mm) 8 feet (2,438 mm)
<br /> Property line adjoining
<br /> private property Clear 5 feet (1,524 mm) 5 feet (1,524 mm) 8 feet (2,438 mm)
<br /> Water supply wells 50 feet (15,240 mm) 50 feet (15,240 mm) 1,000 feet (304,800 mm) 150 feet (45.7 m)
<br /> Streams and other 50 feet (15,240 mm) 50 feet (15,240 mm) 100 feet (30,480 mm) 150 feet (45.7 m)
<br /> bodies of water
<br /> Trees - 10 feet (3,048 mm) - 10 feet (3,048 mm)
<br /> Seepage pits or cesspools - 5 feet (1,524 mm) 5 feet (1,524 mm) 12 feet (3,658 mm)
<br /> Disposal Field - 5 feet (1,524 mm) 4 feet (1,219 mm) 5 feet (1,524 mm)
<br /> On -site domestic water
<br /> service line 1 foot (305 mm) 5 feet (1,524 mm) 5 feet (1,524 mm) 5 feet (1,524 mm)
<br /> Distribution box - - 5 feet (1,524 mm) 5 feet (1,524 mm)
<br /> Pressure public water main 10 feet (3,048 mm) 10 feet (3,048 mm) 10 feet (3,048 mm) 10 feet (3,048 mm)
<br /> Note: When disposal fields and /or seepage pits are installed in sloping ground, the minimum horizontal distance between any
<br /> part of the leaching system and ground surface shall be fifteen (15) feet (4,572 mm).
<br /> ' Includin porches and steps, covered or uncovered, breezeways, porte cocheres, roofed patios, carports,
<br /> Including s p� s Y, P � p �
<br /> covered walks, covered driveways, and similar structures or appurtenances.
<br /> 2 See also Section 313.3 of the Uniform Plumbing Code.
<br /> 3 All drainage piping shall clear domestic water supply wells by at least fifty (50) feet (15,240 mm). This distance may be
<br /> reduced to not less than twenty -five (25) feet (7,620 mm) when the drainage piping is constructed of materials approved
<br /> for use within a building.
<br /> 4 Plus two (2) feet (610 mm) for each additional one (1) foot (305 mm) of depth in excess of one (1) foot (305 mm) below
<br /> the bottom of the drain line. (See also Section K 6.)
<br /> 5 See Section 720.0 of the Uniform Plumbing Code.
<br /> 6 For parallel construction - For crossings, approval by the Health Department shall be required.
<br /> 7 These minimum clear horizontal distances shall also apply between disposal fields, seepage pits, and the mean high tide
<br /> line."