• <br /> Michael Yee • <br /> September 19, 2018 <br /> Page3 <br /> 18.2.3.1.4 When fire department access roads cannot be installed due to location on property, <br /> topography, waterways, nonnegotiable grades, or other similar conditions, the AHJ shall be <br /> authorized to require additional fire protection features. <br /> 18.2.3.2 Access to Building. <br /> 18.2.3.2.1 A fire department access road shall extend to within in 50 ft (15 m) of at least one <br /> exterior door that can be opened from the outside that provides access to the interior of the <br /> building. Exception: 1 and 2 single-family dwellings. <br /> 18.2.3:2.1.1 When buildings are protected throughout with an approved automatic sprinkler <br /> system that is installed in accordance with NFPA 13, NFPA 13D, or NFPA 13R, the distance in <br /> 18.2.3.2.1 shall be permitted to be increased to 300 feet. <br /> 18.2.3.2.2 Fire department access roads shall be provided such that any portion of the facility or <br /> any portion of an exterior wall of the first story of the building is located not more than 150 ft <br /> (46 rn) from fire department access roads as measured by an approved route around the exterior <br /> of the building or facility. <br /> 18.2.3.2.2.1 When buildings are protected throughout with an approved automatic sprinkler <br /> system that is installed in accordance with NFPA 13,NFPA 13D, or NFPA I3R, the distance in <br /> 18.2.3.2.2 shall be permitted to be increased to 4.50 ft(137 m). <br /> 18.2.3.3 Multiple Access Roads. More than one fire department access road shall be provided <br /> when it is determined by the AHJ that access by a single road could be impaired by vehicle <br /> congestion, condition of terrain, climatic conditions, or other factors that could limit access. <br /> 18.2.3.4 Specifications. <br /> 18.2.3.4.1 Dimensions. <br /> C—18.2.3.4.1.1 FDAR shall have an unobstructed width of not less than 2Oft with an approved <br /> turn around area if the FDAR exceeds 150 feet. Exception: FDAR for one and two family <br /> dwellings shall have an unobstructed width of not less than 15,feet,with an area of not less than <br /> 20 feet wide within 150 feet of the structure being protected. An approved turn around area shall <br /> be provided if the FDAR exceeds 250 feet. <br /> C—18.2.3.4.1.2 FDAR shall have an unobstructed vertical clearance of not less then 13ft 6 in. <br /> C—j 18.2.3.4.1.2.1 Vertical clearances may be increased or reduced by the AHJ,provided such <br /> increase or reduction does not impair access by the fire apparatus, and approved signs are <br /> installed and maintained indicating such approved changes. <br />