Laserfiche WebLink
The provisions in 314.23(A) through (H). <br />(A) Surface Mounting. An enclosure mounted on a building <br />Or other surface shall be rigidly and securely fastened in <br />Place. If the surface docs not provide rigid and secure support, <br />Additional support in accordance with other provisions <br />Of this section shall be provided. <br />314.17 Conductors Entering Boxes, Conduit Bodies, or <br />Fittings. Conductors entering boxes, conduit bodies, or <br />Fittings shall be protected from abrasion and shall comply <br />With 314.17(A) through (D). <br />(A) Openings to Be Closed. Openings through which conductors <br />Enter shall be adequately closed. <br />(B) Metal Boxes and Conduit Bodies. Where metal boxes <br />Or conduit bodies are installed with messenger -supported <br />Wiring, open wiring on insulators, or concealed knob -and tube <br />Wiring, conductors shall enter through insulating bushings <br />Or, in dry locations, through flexible tubing extending <br />From the last insulating support to not less than 6 mm (1/4 <br />In.) Inside the box and beyond any cable clamps. Except as <br />Provided in 300.15(C), the wiring shall be firmly secured to <br />The box or conduit body. Where raceway or cable is installed <br />With metal boxes or conduit bodies, the raceway or <br />Cable shall be secured to such boxes and conduit bodies. <br />