(C) Nonmetallic Boxes and Conduit Bodies. Nonmetallic <br />Boxes and conduit bodies shall be suitable for the lowest <br />Temperature-rated conductor entering the box. Where nonmetallic <br />Boxes and conduit bodies are used with messenger supported <br />Wiring, open wiring on insulators, or concealed <br />Knob-and-tube wiring, the conductors shall enter the box <br />Through individual holes. Where flexible tubing is used to <br />Enclose the conductors; the tubing shall extend from the last <br />Insulating support to not less than 6 mm (1/4 in.) inside the <br />Box and beyond any cable clamp. Where nonmetallic sheathed <br />Cable or multiconductor Type UF cable is used, <br />The sheath shall extend not less than 6 mm (1/4 in.) inside <br />The box and beyond any cable clamp. In all instances, all <br />Permitted wiring methods shall be secured to the boxes. <br />Exception: Where nonmetallic-sheathed cable or multiconductor <br />Type UF cable is used with single gang boxes not <br />Larger than a nominal size 57 mm x 100 mm (21/4 in. <br />x 4 in.) Mounted in walls or ceilings, and where the cable <br />Is fastened within 200 mm (8 in.) of the box measured along <br />the sheath and where the sheath extends through a cable <br />Knockout not less than 6 mm (1/4 in.), securing the cable to <br />The box shall not be required. Multiple cable entries shall <br />Be permitted in a single cable knockout opening. <br />