Laserfiche WebLink
For SL• 1 foot = 304.8 mm. <br />NR = No Requirement. <br />a. R- values are minimums. U- factors and SHGC are maximums. <br />b. The fenestration U- factor column excludes skylights. The SHGC <br />column applies to all glazed fenestrations." <br />(17) Adding Table 402.1.1.1. Table 402.1.1.1 is added to read as follows: <br />"TABLE 402.1.1.1 <br />CEILING INSULATION ALTERNATIVE <br />Design <br />Option <br />Design and Construction Components <br />Fenestration U- Factor <br />Roof Insulation <br />Attic Ventilation <br />Radiant <br />Barrier <br />Cool Roof <br />Section <br />Roof Heat Gain <br />Factor below 0.05 <br />(Section 402.1.1.8) <br />1 <br />R <br />Mass Wall U- Factor <br />0.197 <br />Floor U- Factor <br />NR <br />2 <br />NR <br />R <br />R <br />3a <br />R <br />R <br />4a <br />R <br />R = Required <br />a = Design Option is not allowed at building sites above a 2,400 -foot elevation." <br />(18) Amending Table 402.1.3. Table 402.1.3 is amended by deleting all <br />references to Climate Zones 1 through 8 and replacing with a single <br />climate zone, "Hawai`i County ", amending footnote "b ", and deleting <br />footnote "c ", to read as follows: <br />"TABLE 402.1.3 <br />EQUIVALENT U- FACTORS <br />Climate Zone <br />Hawaii County <br />Fenestration U- Factor <br />1.2 <br />Skylight U- Factor <br />0.75 <br />Ceiling U- Factor <br />0.035 <br />Frame Wall U- Factor <br />0.082 <br />Mass Wall U- Factor <br />0.197 <br />Floor U- Factor <br />NR <br />Basement Wall U- Factor <br />NR <br />Crawl Space Wall U- Factor <br />NR <br />NR = No Requirement <br />