Laserfiche WebLink
the distance to the Fire Department Connection may be increased <br />to 1000 feet. <br />(d) For one and two family dwellings, agricultural buildings and <br />storage sheds greater than 2000 square feet, but less than 3000 <br />square feet of living area, that meets the minimum Fire <br />Department Access Road requirements, the distance to the Fire <br />Department Connection may be increased to 500 feet. <br />(e) For buildings with an approved automatic sprinkler system, the <br />minimum water supply required may be modified. <br />Section 26 -43. Occupant Load Sign for Assemblies. <br />20.1.4.10.3.1 is amended to read: <br />20.1.4.10.3.1 Any room or area constituting an assembly, regardless of seating <br />arrangements, shall have a permanent occupant load sign posted in a conspicuous <br />place near the main exit from the room. <br />Section 26 -44. Seating arrangements. <br />20.1.4.10.4 is added to read: <br />20.1.4.10.4 The maximum number of seats permitted between the farthest seat <br />and any aisle shall not exceed that shown in table 20.1.4.10.4. <br />Table 20.1.4.10.4 <br />Application <br />Outdoors <br />Indoors <br />Chair style seating (loose) <br />Bench/ Bleacher type seating <br />11 <br />20 <br />6 <br />9 <br />Section 26 -45. Cooking Operations affiliated with Tents and Temporary structures. <br />25.1.11.1 is added to read: <br />25.1.11.1 Cooking operations shall comply with Section 10.11.3.1 of this code. <br />Section 26 -46. Deep Fat Frying. <br />25.1.11.2 is added to read: <br />25.1.11.2 A minimum of one Type K Fire extinguisher shall be accessible within <br />30 feet of any deep fat frying operation in accordance with NFPA 10. <br />17 <br />